31
INST
ALLER Section
(en)
7219620.01 (1-04/15)
10. INSTALLING THE DUCTS
The boiler is easy and flexible to install thanks to the extensive range of available accessories, as described below. The boiler
has been designed for connection to a vertical or horizontal coaxial flue-air duct. The boiler can also be used with separate ducts
using the accessory splitting kit.
See figure in annex "SECTION" C at the end of this manual.
WARNINGS
C13, C33
The terminals for separate flues must be fitted inside a 50 cm square. Detailed instructions are provided with the
individual accessories.
C53
Do not fit the flue and air duct terminals on opposite walls of the building.
C63
The pressure drop of the ducts must not exceed
100 Pa
. The ducts must be certified for this specific use and for a temperature
in excess of 100°C. The flue terminal must be certified to EN 1856-1.
C43, C83
The flue terminal or flue duct must be suitable for the purpose.
SOME DUCT INSTALLATION EXAMPLES ARE SHOWN AT THE END OF THIS MANUAL, SEE FIGURE IN ANNEX "SECTION" D.
For optimal installation, the accessories supplied by the manufacturer should be used.
To optimise operating safety, make sure the flue ducts are firmly fixed to the wall with suitable brackets. The brackets must be
positioned over the joints at a distance of approximately 1 metre from one another.
10.1 CONCENTRIC DUCTS
This type of duct is used to discharge exhaust fumes and draw
combustion air both outside the building and if a LAS flue is
fitted. The 90° coaxial bend allows the boiler to be connected
to a flue-air duct in any direction as it can be rotated by 360° It
can also be used as a supplementary curve combined with a
coaxial duct or a 45° curve.
If fumes are discharged outside the building, the flue-air
duct must protrude at least 18 mm from the wall to allow an
aluminium weathering surround to be fitted and sealed to
avoid water infiltrations.
•
A 90° bend reduces the total duct length by 1 metre.
•
A 45° bend reduces the total duct length by 0.5 metres.
•
The first 90° bend is not included when calculating the maximum available length.
Secure the intake pipes with two galvanised screws with a diameter of 4.2 mm and a maximum length of 19 mm.
Before securing the screws, make sure that at least 45 mm of the pipe is inserted into the gasket (see the figures in annex
"SECTION" D at the end of this manual).
Make sure there is a minimum downward slope of 5 cm per metre of duct towards the boiler.
SOME OUTLET DUCT INSTALLATION EXAMPLES AND THEIR RELATIVE MAXIMUM LENGTHS ARE SHOWN IN ANNEX
"SECTION" D
AT THE END OF THIS MANUAL.
10.2 SEPARATE DUCTS
This type of installation makes it possible to discharge exhaust
fumes both outside the building and into single flue ducts.
Comburent air can be drawn in at a different location from that
of the flue terminal. The accessory splitting kit comprises a
flue duct adaptor (80) (
B
) and an air duct adaptor (
A
). For the
air duct adaptor, fit the screws and seals previously removed
from the cap.
The 90° bend is used to connect the boiler to the inlet and
outlet ducts, adapting them to various requirements. It can
also be used as a supplementary curve combined with a duct
or a 45° bend.
•
A 90° bend reduces the total duct length by 0.5 metres.
•
A 45° bend reduces the total duct length by 0.25 metres.
•
The first 90° bend is not included when calculating the maximum available length.
Summary of Contents for LUNA DUO-TEC+
Page 112: ...7219620 01 1 04 15 112 S E C T I O N A...
Page 118: ...7219620 01 1 04 15 118 S E C T I O N C 7218789 01 53 5 41 5...
Page 119: ...119 S E C T I O N C 7219620 01 1 04 15 53 5 41 5 A 168 5 53 5 41 5 A 168 5...
Page 120: ...7219620 01 1 04 15 120 S E C T I O N D 25 mm...
Page 123: ...123 S E C T I O N F 7219620 01 1 04 15...
Page 124: ...7219620 01 1 04 15 124 S E C T I O N G...
Page 126: ...7219620 01 1 04 15 126...
Page 127: ...127 7219620 01 1 04 15...