41
INST
ALLER Section
(en)
7219620.01 (1-04/15)
18. ANNUAL SERVICING
If the boiler was operating, wait for the combustion chamber and pipes to cool down.
Before commencing any maintenance operations, make sure the boiler is disconnected from the power supply. After servicing,
reset the original operating parameters of the boiler if they were changed.
Do not clean the boiler with abrasive, aggressive and/or easily flammable substances (such as petrol, acetone, etc.).
To optimise boiler efficiency, carry out the following annual controls:
• Check the appearance and airtightness of the gaskets of the gas and combustion circuits;
• Check the state and correct position of the ignition and flame-sensing electrodes;
• Check the state of the burner and make sure it is firmly fixed;
• Check for any impurities inside the combustion chamber. Use a vacuum cleaner to do this;
• Check the pressure of the heating system;
• Check the pressure of the expansion vessel;
• Check the fan works correctly;
• Make sure the flue and air ducts are unobstructed;
• Check for any impurities inside the siphon (for condensation boilers);
• Check the magnesium anode, where present, for boilers fitted with storage boilers.
It is advisable not to use the service cap at the base to empty and clean the siphon. Remove the siphon from inside the boiler
and clean it with a jet of water. Fill the siphon with clean water and put back in place, making sure that it is properly connected.
18.1 HYDRAULIC UNIT
For special areas, where the water is harder than
20 °F
(1 °F = 10 mg calcium carbonate per litre of water), install a polyphosphate
dispenser or an equivalent treatment system, compliant with current regulations.
LEGEND -
"SECTION" F
A
DHW exchanger fixing screw
B
DHW priority sensor with filter
C
Boiler/system drain tap
(
C-1
&
C-2
:
access to tap
C
- bottom of boiler)
D
Boiler / system filling tap
E
DHW temperature NTC probe
F
Heating circuit water pressure sensor
18.1.1 CLEANING THE COLD WATER FILTER
The boiler is fitted with a cold water filter located on the hydraulic assembly (
B
). To clean, proceed as follows:
• Drain the domestic hot water system.
• Remove the nut on the DHW priority sensor unit
• Pull out the flow sensor and its filter.
• Remove any impurities.
When replacing and/or cleaning the O-rings on the hydraulic assembly, only use Molykote 111 as a lubricant, not oil or grease.
18.2 POSITIONING THE ELECTRODES
5
±1
4
±0
,5
10 ±1
CG_2190
Summary of Contents for LUNA DUO-TEC+
Page 112: ...7219620 01 1 04 15 112 S E C T I O N A...
Page 118: ...7219620 01 1 04 15 118 S E C T I O N C 7218789 01 53 5 41 5...
Page 119: ...119 S E C T I O N C 7219620 01 1 04 15 53 5 41 5 A 168 5 53 5 41 5 A 168 5...
Page 120: ...7219620 01 1 04 15 120 S E C T I O N D 25 mm...
Page 123: ...123 S E C T I O N F 7219620 01 1 04 15...
Page 124: ...7219620 01 1 04 15 124 S E C T I O N G...
Page 126: ...7219620 01 1 04 15 126...
Page 127: ...127 7219620 01 1 04 15...