Parameter
Description of the advanced parameters
EHC–05 factory
setting
Manual Heat
Demand (AP002)
Enable manual heat demand function.
In this mode, the temperature set point used will be that for the
AP026.
0
Setpoint manual
HD (AP026)
Flow temperature setpoint for manual heat demand.
Can be set from 7 to 70 °C
Set point used when manual mode is active (AP002 = 1)
40
Cooling mode
(AP028)
Configuration of the cooling mode
0 = Off
1 = Active cooling on
0
Max CH flow
setpoint (AP063)
Maximum central heating flow temperature setpoint.
Can be set from 20 °C to 75 °C
Electrical back-up:
75
Humidity sensor
(AP072)
Humidity sensor configuration:
0 =No
1 =OnOff
2 =0-10V sensor
0
BL1 contact config.
(AP098)
BL1 input contact configuration:
0 = input active on Open contact
1 = input active on Closed contact
0
BL2 contact config.
(AP099)
BL2 input contact configuration:
0 = input active on Open contact
1 = input active on Closed contact
0
BL2 function
(AP100)
BL2 input function selection
1 = Full blocking of the installation – frost protection not guaranteed
2 = Partial blocking of the installation – installation frost protection
3 = User reset locking
4 = Backup relieved
5 = Generator relieved
6 =Gen.&Backup relieved
7 =High, Low Tariff
8 =Photovoltaic HP Only
9 = PV HP And backup
10 = Smart Grid ready
11 = Not used
2
De-aeration cycle
(AP101)
De-air cycle settings:
0 =No deair at power up
1 =Always deair at pwr
1
9.4.5
Installation Setup > Cascade management B >
Parameters, counters, signals
NP : Network Parameters = Cascade parameters
Tab.78 Parameters
Parameter
Description
Factory setting
SCB-10
Cascade
Permutation
(NP005)
Choice of the leading generator,.AUTO: Switching of order every 7 days
Can be set from 0 to 127
0
Cascade Type
(NP006)
Cascading boilers by adding successively or in parallel, the boilers function
simultaneously
0: Traditional
1: parallel
0
CascTOutsideHeat
Parl (NP007)
Outdoor start temperature heating of all stages in parallel mode
Can be set from -10 °C to 20 °C
10
CascTPostRunGen
ePump (NP008)
Duration of post operation of the cascade generator pump
Can be set from 0 Min to 30 Min
4
9 Settings
7762758 - v05 - 19082020