1
Number of days of drying
2
Drying start temperature
3
Drying end temperature
Important
If the return water temperature is below 10 °C, screed drying will
start using the electrical back-up until the return water reaches a
temperature of 20 °C (to prevent it taking too long, particularly in
winter).
Tab.49 Example: to prepare the screed on which the floor covering will be applied, the parameters need to be adjusted every
seven days
Day
1
Number of days of
drying
2
Drying start temper
ature
3
Drying end temper
ature
Remarks
1 to 7
7
+25 °C
+55 °C or maximum au
thorised flow tempera
ture
In increments of 5 K
8 to 14
7
+55 °C or maximum au
thorised flow tempera
ture
+55 °C or maximum au
thorised flow tempera
ture
No night reduction
15 to 21
7
+55 °C or maximum au
thorised flow tempera
ture
+25 °C
In increments of 5 K
1. Set the parameters for the circuit with screed to be dried.
Tab.50
Access
Adjustment required
Parameter
Description
21.7
CIRCA0,
19.8
, CIRCA1,
CIRCB1 or CIRCC1 > Set
Screed Drying
1
Number of days of dry
ing
Zone screed drying
Setting of the screed drying
program of the zone
2
Drying start temperature ScreedStartTemp
Setting of the start
temperature of the screed
drying program of the zone
3
Drying end temperature ScreedStopTemp
Setting of the stop
temperature of the screed
drying program of the zone
The screed drying programme will start immediately and continue for the
selected number of days.
At the end of the programme, the selected operating mode will restart.
9.2.8
Drying screed without the heat pump outdoor unit
The indoor module can be used for drying screed using the electrical
back-up. It is not necessary to connect the outdoor unit.
1. Switch on the indoor module and activate the screed drying function.
2. Adjust the parameters for screed drying.
If the outdoor unit is not connected, the back-ups will start
automatically.
Fig.62
MW
-5000764-2
10
9
8
7
6
5
4
3
2
1
23
20
26
29
32
35
38
41
44
47
° C
00:00
00:00
00:00
1
2
3
On
Fig.63
MW
-1000988-1
9 Settings
7762758 - v05 - 19082020
61