3.1.8
The minimum height from the top surface of the hearth to the underside of any
shelf made from wood or other combustible materials is detailed below.
!
For a shelf up to 150mm deep
: Minimum height = 700mm.
!
For a shelf deeper than 150mm
: 700mm + 12.5mm for every 25mm depth over
150mm (See Graph 1).
3.1.9
The front face of the wall should be reasonably flat over the area that will be
covered by the fire box top and side flanges to ensure a good seal. The minimum height
from the top surface of the hearth to the underside of any shelf made from wood or
other combustible materials is as follows:-
Note that soft wall coverings (e.g. embossed vinyl, etc.) are easily affected by heat.
They may scorch or become discoloured when close to a heating appliance. Please bear
this in mind when installing.
3.1.10
The appliance must not be installed in any room that contains a bath or shower or
where steam is regularly present.
3.1.11
An extractor fan may only be used in the same room as this appliance, or in any
area from which ventilation for the appliance is taken, if it does not affect the safe
performance of the appliance. Note the spillage test requirements detailed further on in
this manual. If the fan is likely to affect the appliance, the appliance must not be
installed unless the fan is permanently disconnected, or provision is made to ensure that
the fan and the appliance cannot be used at the same time.
A fan-powered flue system tends to depressurise the room containing the appliance.
Page 8
INSTALLER GUIDE
Graph 1.