!
When the pilot is alight and stable, partially depress the knob and turn to “LOW”.
The pilot should then light the main burner at its low setting. There may be a delay of
up to four seconds between the pilot lighting and ignition of the gas at the main burner.
This is normal and is due to the time required to fill the main burner compartment with
sufficient gas for ignition.
!
When the burner is lit, partially depress the knob and gradually turn it anti-
clockwise. The burner flames should gradually increase until the knob reaches the
“HIGH” position.
!
Partially depress the control knob and turn back to “PILOT/IGN”. The main burner
flames should be extinguished but the pilot should remain alight.
!
Partially depress the control knob and turn to “OFF”. The pilot should be
extinguished.
!
Press the “off” switch to turn off the fan (the indicator light should glow).
12.2 Check for spillage.
!
Close all doors and windows in the room containing
the appliance.
!
Turn on the fan
.
Light the appliance and turn the
control knob to “HIGH”.
!
Leave the appliance on for five minutes.
!
Place the smoke match tube into the burner box below
the hood (See figure 41).
!
The installation is satisfactory if the smoke is drawn
into the appliance. If the smoke is not drawn into the
appliance the fan powered extraction system is not
operating correctly.
Do not allow the appliance to be used
until the fault is corrected.
!
If the above test is satisfactory, open all internal
connecting doors, hatches, etc. in the room. Keep all doors
and windows that open to the outside of the building
closed. Recheck for spillage as above. If an extractor fan or other air circulating system
is installed in the same room as the appliance or a connecting room, check that spillage
does not occur with the fan operating and all doors and other openings between the fan
and the appliance open.
!
If the smoke is drawn into the appliance, continue with the installation. If the test is
not satisfactory,
Disconnect the appliance and seek expert advice.
Page 34
INSTALLER GUIDE
Figure 41.
A spillage check must be made before leaving the installed appliance with the
customer. Make this check with the appliance fully installed with the ceramic fuel
effects and fascia in position.