PD-TaD 80
Product information
822-188-3
21 / 74
No.
Element
Function
1
Protective earthing port
(metal port)
Is used to connect the protective earthing
2
Signal output (black port)
Is used for connection to the test object.
3
Display of selected charge in
[nC]
4
Range
Is used for setting the calibration charge
Possible settings:
CAL1B: 0.10, 0.20, 0.50, 1.00, 2.00, 5.00, 10.00 nC
CAL1E: 0.50, 1.00, 2.00, 5.00, 10.00, 20.00, 50.00 nC
5
Pos/Neg
Press briefly to set the polarity of the signal.
On/Off
To switch on, press briefly.
To switch off, press for approx. 3 seconds.
Note that the calibrator must be removed from the test circuit before switching on the
high voltage source.
Note:
After some time, the calibrator automatically switches off to extend the battery life. If
you have not yet completed the calibration, switch on the calibrator.