Alarms
menu
The functionality and available capabilities of the flow
sensor vary depending on the order configuration and
type code.
Depending on the configuration of the flow sensor or
activated functions, individual menus and selection
functions may differ from the representations or be
hidden.
Menu
Description
Password level /
BCP command
Max.thr+
Maximum value for positive flow
If the maximum value for the positive flow
exceeds the set value, an alarm message is
generated.
The value of this parameter is set as a per-
centage (0 - 125%) of the scale end value.
If the parameter is 0, the alarm generation is
deactivated.
L 3
FRAXP
Max.thr-
Maximum value for negative flow
If the maximum value for the negative flow
exceeds the set value, an alarm message is
generated.
The value of this parameter is set as a per-
centage (0 - 125%) of the scale end value.
If the parameter is 0, the alarm generation is
deactivated.
L 3
FRAXN
Min.thr+
Minimum value for positive flow
If the minimum value for the positive flow falls
below the set value, an alarm message is gen-
erated.
The value of this parameter is set as a per-
centage (0 - 125%) of the scale end value.
If the parameter is 0, the alarm generation is
deactivated.
L 3
FRANP
Operation
Menu navigation > Alarms menu