7.6.4
Measure
menu
The functionality and available capabilities of the flow
sensor vary depending on the order configuration and
type code.
Depending on the configuration of the flow sensor or
activated functions, individual menus and selection
functions may differ from the representations or be
hidden.
Menu
Description
Password level /
BCP command
Damping
Damping filters
The choice of damping filter, depending on the
system requirements, is crucial for the accurate
measurement of flow rate.
L 3
MFDMP
Cut-off
Threshold for low flow
This function prevents a near-zero flow rate
due to electrical noise or minute flow (such as
tube vibration) from increasing the total meter.
The threshold can be0 - 25% of the set scale
end value.
A value between 0.5 and 1 % is recommended
for most applications.
L 3
MFCUT
Operation
Menu navigation > Measure menu
05.03.2020
Flow sensor PF55S
68