WARNING!
Danger due to leaking system
Leaks in the system may occur when the flow sensor is
installed within a piping system. These leaks can lead
to a variety of different dangers.
The following must be observed when installing the
flow sensor:
–
The inner diameter of the seals is always equal to
or greater than the inner diameter at the connection
of the pipeline.
–
Seals must always be checked for damage and
cleanliness.
–
Seals must always be properly installed.
CAUTION!
Short circuit of the measuring signal due to incor-
rect sealing compound
If impermissible sealing compounds are used, an elec-
trically conductive layer can form on the inside of the
measuring tube of the sensor. As a result, short circuits
of the measuring signal are possible.
–
Never use electrically conductive sealing com-
pounds such as graphite.
5.
Install the flow sensor in the intended position.
Pay attention to the following:
n
Only approved installation tools may be used for the
flanges and process connections.
n
All transition pieces, fittings and the like must be firmly
connected and sealed.
n
Only suitable and approved lubricating pastes or sealing
compounds may be used.
n
The flow sensor must be installed in the correct flow
direction.
n
The sensor must be firmly and securely installed in the
pipeline with seals.
n
All torques must be observed during assembly.
6.
Check the piping system for leaks in the area of the flow
sensor.
7.
Connect the flow sensor electrically.
5.4 “Electrical connection” on page 38
ð
The flow sensor PF55S is installed.
Assembly and installation
Installation
05.03.2020
Flow sensor PF55S