PCD41
www.baumer.com
41
Momentary indication of A/D value.
Enter maximum value using key
.
Maximum value is dopted.
Indicated in the display for 1 s, then followed by
the assigned value. Key
= back to operation
mode. Press key
until the actual measured
value (F) is indicated.
The alignment operation runs also in operating mode. In this case,
settings for bFdn (line 13) and bFuP (line 14) in programming ield 2
must be „0“.
6 Technical data
Technical data - electrical ratings
Voltage supply
115/230 VAC ±10 % (50/60 Hz)
24/48 VAC ±10 % (50/60 Hz)
12...30 VDC
Power consumption
6 VA, 4 W
Sensor supply
12...26 VDC / max. 80 mA
Display
LED, 7-segment display
Number of digits
6-digits
Digit height
14 mm
Function
Digital display of 1 analog
measured value
Input logic
PNP
Control inputs
2 inputs
Control functions
Hold, reset, keylock, etc.
Data memory
>10 years in EEPROM
Analog input
0(2)...10 V, 0(4)...20 mA
Resolution 12 bit
Temperature coeficient
typically ±20 ppm/ºC
Outputs relay
Normally open / closed, programmable
Interfaces
RS232, RS422, RS485
Standard DIN EN 61010-1
Protection class II
Overvoltage category II
Pollution degree 2
Emitted interference
DIN EN 61000-6-3
Interference immunity
DIN EN 61000-6-2
Programmable parameters
2 limits, analog input,
control inputs, calculating functions,
offset (maximum and minimum
analog limit)