PCD41
www.baumer.com
39
The alignment operation runs also in operating mode. In this case,
settings for bFdn (line 13) and bFuP (line 14) in programming ield 2
must be „0“.
b) Two-point alignment by Teach-In
The two-point alignment by Teach-In enables lexible calibration of
the indicated value to the 10 V respectively 20 mA analog signal.
The reference points 1 and 2 can optionally be set anywhere within
the visualized positive measuring range. See ig. 1 and 2.
Prior to the alignment, enter the following settings in programming
ield 3: line 41 = 0; in line 26 the offset.
Positive
Digit value
Analog value
10 V/20 mA
Balancing point 2
Balancing point 1
0
Fig. 1: Positiv value
Positive
Digit value
Analog value
10 V/20 mA
Balancing point 2
Negative
Digit value
Balancing point 1
0
Fig 2: Positiv and negativ value