PCD41
30
www.baumer.com
3.5 Sensor supply connection
Connect sensor supply to contacts 7 and 8. However, do not use
sensor supply for unearthed inductors or capacitive loads.
The sensor supply is not short-circuit-proof.
Pin
Voltage
Max. admissible current
8
12...26 VDC
80 mA
7
0 V
3.6 Interface connection
The serial interface can perform the following functions:
-retrieve data,
-program and retrieve parameters.
Interface parameters are:
-transmission speed (Baud rate),
-parity bit,
-number of stop bits,
-address by which the master approaches the control instrument.
The interface parameters can be set on the programming level
(line 51 to 56).
RS232
Full-duplex transmission with the following features:
-asymmetric
-3 lines
-point-to-point connection - 1 emitter and 1 receiver
-distance of data transfer: max. 30 m
RS422
Full-duplex transmission with the following features:
-symmetric
-4 lines
-point-to-point connection - emitter and receiver (max. 32 units)
-distance of data transfer: max. 1500 m
RS485
Half-duplex transmission with the following features:
-symmetric
-2 lines
-multi-point connection - emitter and receiver (max. 32 units)
-distance of data transfer: max. 1500 m