Barnett Engineering B1277 Installation & Operation Manual Download Page 47

GLOSSARY 

PAGE 43 

Dial Control

 – a function that, when enabled, delays alarm annunciation 

until the recipient of the call speaks into the phone. (eg. “Hello”) 
 

Digital Input

 – an input type that, when asserted, generates an alarm 

condition.  This input type may be configured as asserted by grounding the 
input terminal, opening the input terminal, or providing a voltage to the 
input terminal that crosses a 2VDC threshold. 
 

Dipole Antenna

 – an RF antenna with a simple structure.  The dipole 

antenna included with the Cv3 is intended for indoor use only and has 
limited range. 
 

Directory

 – a list of callout instructions that are executed sequentially 

when an alarm occurs.  Each directory line may specify a telephone 
number to call, a radio transmission with paging tones, or a mobile 
number to send a text message to.  
 

DTMF

 – Dual Tone Multiple Frequency; a series of audible tones used for 

remote command and control of equipment 
 

ESN

 – 

see Electronic Serial Number

 

 

Electronic Serial Number

 – a permanent 32-bit number embedded by the 

manufacturer that uniquely identifies a wireless communications device. 
 

Group

 – a means of having the alarms created by some inputs respond 

differently than the others.  By default, Groups are not used and all alarms 
are treated the same.  If groups are created, inputs may be individually 
assigned to the group where separate acknowledge and interrogate codes 
are defined and the directories used have unique lists of callout 
instructions. 
 

GSM

 – Global System for Mobile Communications - a mobile telephony 

standard used by carriers such as AT&T Mobility, T-Mobile, and Rogers 
Wireless. 
 

Hysteresis

 – a dead zone around a low and high alarm setpoint that 

requires the input to change sufficiently after creating an alarm before the 
level is recognized as being normal again.  The hysteresis value should be 
set larger than the natural short term variations found on an analog input. 
 

Interval Input

 – an input type that measures the amount of time the input 

has been asserted.  Each time the input is asserted, the count is reset to 
zero.  When the input is de-asserted, the measured value is maintained 
until the next measurement begins. 

Summary of Contents for B1277

Page 1: ...Installation Operation Manual January 2011 Rev 2 0 215 7710 5th St S E Phone 403 255 9544 Calgary Alberta Canada Fax 403 259 2343 T2H 2L9 www barnett engg com e mail sales barnett engg com...

Page 2: ......

Page 3: ...TS 5 WIRING YOUR OUTPUTS 7 5 PROGRAMMING 8 PROGRAMMING WITH A PC 8 PROGRAMMING WITH A HANDSET 9 HANDSET PROGRAMMING CODES 10 6 TESTING THE INSTALLATION 31 7 OPERATIONS 32 8 SPECIFICATIONS 37 9 TECHNIC...

Page 4: ......

Page 5: ...g a remote telephone for control of external equipment Configuration of the ProTalk Cv3 can be accomplished using the dedicated PC application using a local programming telephone or by remotely callin...

Page 6: ...or Mobile Directory Number MDN Additionally to program the Cv3 and the embedded transceiver one of the following is required Standard telephone set with DTMF keypad or Personal Computer with CD Drive...

Page 7: ...internal battery charger operates with input voltages between 8 and 30 volts DC The internal battery is limited to 1 4Ahr if you require a larger battery capacity please contact our sales office for...

Page 8: ...sales office if your needs exceed the limits of this antenna as we may be able to supply or recommend an appropriate substitute Installation using a two way radio or public address system The radio po...

Page 9: ...e or terminal for inputs 7 through 10 Technical drawings have been provided on page 41 for your reference In addition to the standard detection of an alarm state at the input a digitally formatted inp...

Page 10: ...s DC and 0 to 30 volts DC For analog voltage operation connect the signal to the single terminal for inputs 1 through 6 and either the or terminal for inputs 7 through 10 Inputs 7 through 10 are also...

Page 11: ...an be programmed as new alarm present any alarm present a pulsed output when an acknowledgement is received or as a system alarm When used for status indicators specific relays are assigned as follows...

Page 12: ...ill ask you if you want Windows Update to search for software select No not at this time You will then be prompted for an installation CD This is the software that was provided to you and should still...

Page 13: ...Programming For a remote session call in to the B1277 from your TouchTone telephone set When answering an incoming call this unit responds depending on the previously programmed Security Level setting...

Page 14: ...five seconds the Cv3 will announce the menu choices Voices page 11 Directories page 12 General Site Configuration page 14 Input Configuration page 16 Output Configuration page 22 Group and Shift Conf...

Page 15: ...oices Exit to Main Menu Exit to Main Menu Playback or Record Voices Cv3 Site is Ajax Compressor Station or Input 1 is Low Temperature or Output 1 is Yard Lights You Record new voice Exit to voice menu...

Page 16: ...to the command list that follows for the available directory entries Cv3 Directory Group 1 Shift 1 Line 1 is or Directory Line 1 is DIAL 2559544 VOICE You Edit current line Erase current line Insert l...

Page 17: ...llowing Quick Commands DIAL VOICE is the telephone number RADIO ALERT VOICE WAIT is the time in seconds 255 SMS TEXT is the data phone number Custom Sequences Custom sequences are created by selecting...

Page 18: ...0 off 1 30 min 2 60 min 3 120 min 4 240 min Exit to Main Menu Next setting Cv3 Relay voices are You Enter new value 0 off 1 on Exit to Main Menu Next setting Cv3 Security Level is You Enter new value...

Page 19: ...gits hours 01 02 04 06 08 or 012 hours 1 to 7 digits days 1 Monday 2 Tuesday Exit to Main Menu Next setting Cv3 Auto Report Radio is You Enter new value 0 off 1 on Exit to Main Menu Next setting Cv3 A...

Page 20: ...input 7 5 volt analog input 8 30 volt analog input 9 Current input 10 System Acknowledge input 11 System Shift select input Exit to Main Menu Next setting for this input Menu items for Digital Inputs...

Page 21: ...Main Menu Next setting Cv3 Input Level is You Enter new value 1 normally high or transition to low 2 normally low or transition to high 3 either transition Exit to Main Menu Next setting Cv3 Time Scal...

Page 22: ...e 1 seconds 2 minutes Exit to Main Menu Next setting Menu items for Totalizer Inputs are Cv3 Input N Is You Enter new value 0 disabled 1 enabled 1 to 6 new group member Exit to Main Menu Next setting...

Page 23: ...ue 0 disabled 1 enabled 1 to 6 new group member Exit to Main Menu Next setting Cv3 Input Level is You Enter new value 1 normally high or transition to low 2 normally low or transition to high 3 either...

Page 24: ...enu Next setting Cv3 Input Level is You Enter new value 1 normally high or transition to low 2 normally low or transition to high 3 either transition Exit to Main Menu Next setting Cv3 Timeout Interva...

Page 25: ...A high setpoint must be within the Decimal Minimum and Maximum and must not be less than the Low Setpoint Hysteresis value Exit to Main Menu Next setting Cv3 Setpoint Low is You Enter new value Enter...

Page 26: ...for this input Menu items for Manual On Off Outputs are Cv3 Output One Type is On Off Cv3 Output Format is You Enter a new value 0 NO contacts 1 NC contacts Exit to Main Menu Next setting Cv3 DTMF On...

Page 27: ...value 1 seconds 2 minutes Exit to I O Configurations Next Setting Cv3 Output Time is You Enter new value 1 to 65535 Exit to Main Menu Next Setting Menu items for Automatic On Off Outputs Relays 1 2 o...

Page 28: ...e 0 NO contacts 1 NC contacts Exit to Main Menu Next setting Cv3 Output Scale is You Enter new value 1 seconds 2 minutes Exit to I O Configuration Next Setting Cv3 Output Time is You Enter new value 1...

Page 29: ...etting Cv3 Interrogate Code is You Enter a new DTMF code Exit to Main Menu Next setting Cv3 Directory Timer is You Enter new value 1 to 255 min Exit to Main Menu Next setting Cv3 Acknowledge Request i...

Page 30: ...sec steps Exit to Main Menu Next setting Cv3 Radio Volume One is minus TX Tone You Enter a new value 0 to 20 Exit to Main Menu Next setting Cv3 Radio Volume Two is minus TX DTMF You Enter a new value...

Page 31: ...PROGRAMMING PAGE 27 Reset Database Cv3 Empty Program Cv3 Alert Enter Octo Three One Star Star You Confirm Exit to Main Menu Exit to Main Menu Cv3 Program is Empty...

Page 32: ...rogate Phone Cv3 Signal Strength is 0 to 15 3 poor 6 good You Exit to Main Menu Next item Cv3 PRL is PRL You Exit to Main Menu Next item Cv3 SID is SID You Exit to Main Menu Next item Cv3 Roaming stat...

Page 33: ...The Phone Control is a parameter predefined by the cellular service provider and is automatically programmed into the module Contact Barnett Technical Support prior to changing this parameter Cv3 Pro...

Page 34: ...rsion Cv3 Serial Number is You Exit to Main Menu You Next Cv3 Hardware version is You Exit to Main Menu You Next Cv3 Firmware version is You Exit to Main Menu You Next Cv3 Options are You Exit to Main...

Page 35: ...d Red see RSSI 0 RSSI 0 see No Service 4 Flashing Red Invalid MIN and no service Flashing Red 4 Flashing Red Invalid MIN and service Flashing Green 1 to 4 Solid Green Invalid MIN and roaming Flashing...

Page 36: ...eaches the end of the directory without being acknowledged it will wait two minutes Directory Timer then start calling again beginning at the top of the directory In addition to making voice calls the...

Page 37: ...phrase No Alarms and then prompt you to Enter Command Code The B1277 then waits ten seconds for you to enter one of the following user defined control codes Acknowledge code Interrogate code Totalize...

Page 38: ...tem alarm If the input is disabled Off If the input is enabled Configured as an alarm input digital analog watchdog Idle no alarm Off Alarm is unacknowledged Flashing Red Alarm is acknowledged Solid R...

Page 39: ...y Solid Red 4 SIGNAL Refer to the Signal Telephone Status table found on Page 32 5 OUTPUT 4 one for each output relay If the relay is in the idle state Off If the relay is in the ON state Solid Red If...

Page 40: ...disconnected from the primary power source and operating from the internal battery pressing the power switch continuously for 5 seconds will cause the unit to power down Normal operation will be resto...

Page 41: ...0 All inputs will withstand up to 30 VDC Inputs 1 to 6 Analog voltage mode Input impedance 210k ohm Range 0 to 5 or 0 to 30 VDC Digital mode Internal 4 7k ohm pull up resistor to 5 VDC Operates with g...

Page 42: ...capacitor coupled Adjustable between 0 dBm and 20 dBm RX audio 600 ohms single ended capacitor coupled Adjustable between 0 dBm and 20 dBm Program Ports Telset RJ11 connector Internal telset bias fro...

Page 43: ...TECHNICAL DRAWINGS PAGE 39 9 TECHNICAL DRAWINGS Unit Dimensions...

Page 44: ...PAGE 40 TECHNICAL DRAWINGS Wiring Inputs Digital connection Inputs 1 through 6 Digital connection Inputs 7 through 10 Analog Connection DC Voltage Inputs 1 through 6...

Page 45: ...TECHNICAL DRAWINGS PAGE 41 Analog Connection DC Voltage Inputs 7 through 10 Analog Connection DC Current Inputs 7 through 10...

Page 46: ...low alarm setpoint with an accepted range on the input terminal of 0 to 5 VDC Carrier Operated Squelch an output from a radio that indicates the receiver squelch is open This signal is used by the Pro...

Page 47: ...er a permanent 32 bit number embedded by the manufacturer that uniquely identifies a wireless communications device Group a means of having the alarms created by some inputs respond differently than t...

Page 48: ...ush To Talk Pulse Width see Interval Input Push To Talk an output from the Cv3 that provides a ground closure when a radio transmission is required and an open circuit when idle a k a Push To Transmit...

Page 49: ...support barnett engg com Product Repairs For all your repair needs please contact Barnett Engineering Ltd Barnett Engineering Ltd commits to a Repair Turnaround Time of thirty 30 business days on all...

Page 50: ...ne on account of buyer 1 Consequential Damages Barnett Engineering Ltd shall not be liable for any incidental or consequential damages incurred as a result of any defect in any equipment sold hereunde...

Reviews: