Control Connections
L1
L3
EMC
L2/N
U
V
W
1 2 3 4 5 6 7 8 9 10 11
I0I0I
I0I0I
A
B
C
A
Serial RS485 Port
B
Ethernet Ports (Factory fit option)
C
Control Terminals
Control Terminal Wiring
All analog signal cables should be suitably shielded.
Twisted pair cables are recommended.
Power and Control Signal cables should be routed
separately where possible, and must not be routed parallel
to each other.
Signal levels of different voltages e.g. 24 Volt DC and 110
Volt AC, should not be routed in the same cable.
Maximum control terminal tightening torque is 0.5Nm.
Control Cable entry conductor size: 0.05 – 2.5mm
2
/ 30
– 12 AWG.
Control Terminal Connections
Control Switched Units:
May use the built in control switch and potentiometer, or external control signals connected to the
control terminals.
Non-Switched Units:
Require external control signals to be connected to the control terminals.
Using the Control Terminals
Connection Example
+24
VDC
DI1
DI2
DI3
AI2
+10
VDC
DI4
AI1
0V
A0
0V
RL1
RL2
No.
Purpose
Function
1
+24VDC 100mA Output
24 VDC Output
2
DI1 Digital Input 1
Function defined
by P-12 & P-15.
See below for further info
3
DI2 Digital Input 2
4
DI3 Digital Input 3/AI2 Analog Input 2
5
+10VDC 10mA Output
10 VDC Output for external potentiometer
6
DI4 Digital Input 4/AI1 Analog Input 1
Function defined by P-12 & P-15. Signal format selected by P-16
7
0VDC Common
8
AO Analog Output/Digital Output
Function selected by P-25. See Parameter List
9
0VDC Common
10
RL1 Output Relay
Function defined by P-18. See Parameter List
11
RL2 Output Relay
Factory Default Functions
No.
Description
DI1
0/1
Open : Stop
Closed : Run
DI2
/
Open : Forward Rotation
Closed : Reverse Rotation
DI3
Analog Speed Reference /
Preset Speed
Open : Speed Reference set by Analog Speed Reference
Closed : Speed Reference set by Preset Speed 1 (P-20)
AI1
Analog Speed Reference
Input
Sets the Speed Reference
NOTE
For Switched units, the internal pot is selected by default in P-16.
For Non-switched units, an external pot or 0 - 10 V reference may be connected. Other
signal types may also be used, set P-16 to the correct format.
NOTE
Additional functions are possible, refer to the online documentation for further information.