Technical Data
Environment
Operational ambient temperature range
Enclosed Drives:
-20 ... 40°C (frost and condensation free)
Storage ambient temperature range: -40 … 60°C
Maximum altitude:
2000m. Derate above 1000m: 1% / 100m
Maximum humidity:
95%, non-condensing
Rating Tables
Frame
Size
kW
HP
Input
Current
Fuse/MCB
(Type B)
Maximum Cable
Size
Output
Current
Recommended
Brake Resistance
Non UL
UL
mm
AWG
A
Ω
110 - 115 (+ / - 10%) V 1 Phase Input, 230V 3 Phase Output (Voltage Doubler)
1
0.37
0.5
7.8
10
10
8
8
2.3
-
1
0.75
1
15.8
25
20
8
8
4.3
-
2
1.1
1.5
21.9
32
30
8
8
5.8
100
200 - 240 (+ / - 10%) V 1 Phase Input, 3 Phase Output
1
0.37
0.5
3.7
10
6
8
8
2.3
-
1
0.75
1
7.5
10
10
8
8
4.3
-
1
1.5
2
12.9
16
17.5
8
8
7
-
2
1.5
2
12.9
16
17.5
8
8
7
100
2
2.2
3
19.2
25
25
8
8
10.5
50
3
4
5
29.2
40
40
8
8
15.3
25
200 - 240 (+ / - 10%) V 3 Phase Input, 3 Phase Output
1
0.37
0.5
3.4
6
6
8
8
2.3
-
1
0.75
1
5.6
10
10
8
8
4.3
-
1
1.5
2
8.9
16
15
8
8
7
-
2
1.5
2
8.9
16
15
8
8
7
100
2
2.2
3
12.1
16
17.5
8
8
10.5
50
3
4
5
20.9
32
30
8
8
18
25
3
5.5
7.5
26.4
40
35
8
8
24
20
4
7.5
10
33.3
40
45
16
5
30
15
4
11
15
50.1
63
70
16
5
46
10
380 - 480 (+ / - 10%)V 3 Phase Input, 3 Phase Output
1
0.75
1
3.5
6
6
8
8
2.2
-
1
1.5
2
5.6
10
10
8
8
4.1
-
2
1.5
2
5.6
10
10
8
8
4.1
250
2
2.2
3
7.5
16
10
8
8
5.8
200
2
4
5
11.5
16
15
8
8
9.5
120
3
5.5
7.5
17.2
25
25
8
8
14
100
3
7.5
10
21.2
32
30
8
8
18
80
3
11
15
27.5
40
35
8
8
24
50
4
15
20
34.2
40
45
16
5
30
30
4
18.5
25
44.1
50
60
16
5
39
22
4
22
30
51.9
63
70
16
5
46
22
NOTE
Cable sizes shown are the maximum possible that may be connected to the drive. Cables should be selected
according to local wiring codes or regulations at the point of installation.