background image

Asynchronous Induction Motors (IM) Vector Control

The E3 drive factory default parameters are intended for use with IM motors where the power rating of the motor is 

approximately the same or slightly less than the indicated power rating of the drive. In this case, it should be possible to 

operate the motor without any parameter adjustment at all for initial testing.
For optimum performance, the drive parameters should be adjusted to match the motor ratings. This will also ensure correct 

protection of the motor from damage due to overload.
The basic parameters that should be adjusted are:

 

 P-07 : Motor Rated Voltage (V)

 

 P-08 : Motor Rated Current (A)

 

 P-09 : Motor Rated Frequency (Hz)

In addition, it is also possible to set:

 

 P-10 : Motor Rated Speed (RPM)

When this parameter is adjusted, slip compensation is activated. Slip compensation attempts to compensate the motor speed 

relative to the load applied, such that when operating at a constant speed with different loads, the motor shaft speed should 

remain approximately the same.
To further improve the performance of the motor, the following additional steps can be followed:

 

 Carry out an Autotune.

  o  This requires Advanced Parameter Access, P-14 = P-37 + 100 (Default : 201).
  o   After the correct nameplate information is entered from the motor, the drive can additionally measure some electrical 

characteristics of the motor to further optimise the motor control to suit connected motor.

  o  This is achieved by setting P-52 = 1.
The autotune will begin IMMEDIATELY following the setting of this parameter!
  o   The drive output will be enabled, and the motor shaft may move. It is important to ensure this is safe before carrying out 

the autotune.

  o   For IM motors, the autotune takes only a few seconds, and measures only the motor stator resistance. Parameter P-55 will 

be updated with the new value.

 

Adjust the Low Frequency Torque Boost

  o   IM motors require some additional voltage at low frequency to improve the low speed operation and torque.
  o   By adjusting P-11, it is possible to optimise the low speed operation.
  o   If P-11 is increased too far, excessive motor heating or over current trips may result.

  

Speed regulation and response to load changes may be improved by adjusting P-11 Vector Gain to suit the motor and 

connected load.

  o   Higher values will provide a more dynamic behaviour at the risk of instability.

NOTE

 For other motor types refer to online document. 

Summary of Contents for E3 Series

Page 1: ...Quick Start Guide AC Variable Speed Drive IP66 NEMA 4X 0 37kW 22kW 0 5HP 30HP 1 10V 480V 3 Phase input...

Page 2: ...tage 1 1 10 1 15 2 200 240 4 380 480 No Of Input Phases Output Current x 10 2 PREPARE Prepare the Mounting Location The drive must be mounted in a vertical position only Installation should be on a su...

Page 3: ...Mounting Clearance Drive Size X Above Below Y Either Side mm in mm in All Frame Sizes 200 7 87 10 0 39 NOTE Typical drive heat losses are approximately 3 of operating load conditions Above are guideli...

Page 4: ...egulations Maximum dimensions are given in the Rating Tables section of this Quick Start Guide Install the Power Wiring Single phase supply 3 phase supply L1 L3 EMC L2 N U V W 1 2 3 4 5 6 7 8 9 10 11...

Page 5: ...uide For Canadian installations transient surge suppression must be installed on the line side of this equipment and shall be rated 480Volt phase to ground 480 Volt phase to phase suitable for over vo...

Page 6: ...tch FWD T1 T2 External User Switches VFD Control Terminals 24V DC OR Run Forward P 64 3 DI1 T2 AND Switch FWD OR T2 AND Switch REV T1 T2 External User Switches VFD Control Terminals 24V DC AND Run For...

Page 7: ...rpose Function 1 24VDC 100mA Output 24 VDC Output 2 DI1 Digital Input 1 Function defined by P 12 P 15 See below for further info 3 DI2 Digital Input 2 4 DI3 Digital Input 3 AI2 Analog Input 2 5 10VDC...

Page 8: ...t 2 e g 0 10 Volt 4 20mA Example Connection Diagrams The diagrams below provide an overview of the functions of each terminal macro function and a simplified connection diagram for each Diagram 1 Diag...

Page 9: ...ART the drive in the reverse direction NC STOP Input must be maintained FAST STOP P 24 When both inputs are momentarily active simultaneously the drive stops using Fast Stop Ramp Time P 24 FAST STOP P...

Page 10: ...AI1 3 FAST STOP P 24 8 STOP RUN FWD REV DI3 DI4 PR 2 0 0 P 20 1 0 P 21 0 1 P 22 1 1 P 23 9 STOP START FWD STOP START REV DI3 DI4 PR 2 FAST STOP P 24 0 0 P 20 1 0 P 21 0 1 P 22 1 1 P 23 10 NO START ST...

Page 11: ...d once for each rising edge The step of each speed change is defined by the absolute value of Pre set Speed 1 P 20 Speed change only happens during normal running condition no stop command etc Digital...

Page 12: ...Fire Mode AI1 PI FB 1 17 STOP RUN P 21 REF P 23 REF Fire Mode AI1 PI FB 1 18 STOP RUN AI1 REF PI REF Fire Mode AI1 PI FB 1 2 9 10 11 12 13 Behavior as per setting 0 NOTE P1 Setpoint source is selecte...

Page 13: ...e Navigate key for 1 second The display will show the motor power kW If P 10 0 pressing the Navigate key for 1 second will display the motor speed RPM Changing Parameters Press and hold the Navigate k...

Page 14: ...of zero all speed related parameters are displayed in Hz Entering the value from the motor nameplate enables the slip compensation function and the drive display will also now show motor speed in RPM...

Page 15: ...utput Power 1 1 Load Current P 30 Start Restart Fire Mode Configuration Index 1 Start Mode Auto Restart N A Edge r Following Power on or reset the drive will not start if Digital Input 1 remains close...

Page 16: ...gnal trip on loss r 20 4 External 20 4mA signal ptc th Motor thermistor P 48 Standby Mode Timer 0 0 25 0 0 0 s P 49 PI Control Wake Up Error Level 0 0 100 0 5 0 P 50 User Output Relay Hysteresis 0 0 1...

Page 17: ...ps can be followed Carry out an Autotune o This requires Advanced Parameter Access P 14 P 37 100 Default 201 o After the correct nameplate information is entered from the motor the drive can additiona...

Page 18: ...9 2 25 25 8 8 10 5 50 3 4 5 29 2 40 40 8 8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 8 9 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2...

Page 19: ...to circulate around the drive 09 Under temperature The drive temperature is below the minimum limit and must be increased to operate the drive 10 Factory Default parameters loaded 1 1 External trip E...

Page 20: ...and completely homogeneous systems integration for all Bardac AC and DC drive models drive web smart programmmable controllers flexible i o and savvyPanel industrial touch screens Easily build a compl...

Page 21: ...ting started Get smart see the training videos at https driveweb com training videos Get a speedy model dw228 low cost online now from www AutomationThings com plug your speedy into the drive I O I po...

Page 22: ...p parameters For example click on the Motor Control function block to see the associated parameters and their state or value Click on a parameter to change its value IMPORTANT Your changes take place...

Page 23: ...r into a savvyPanel HMI display Drag and drop any parameter onto system parameter to make a connection Set the parameters monitor the drive state as if you were setting through the drive display and k...

Page 24: ...www driveweb com for training videos and support Once you have a drive web speedy or smarty connected to your drive you can start to build smart control systems using intuitive graphical function blo...

Reviews: