| E3 IP66 Outdoor Rated User Guide |
7
www.bardac.com
Mech
anical Installation
3
3. Mechanical Installation
3.1. General
The E3 drive should be mounted in a vertical position only, on a flat, flame resistant, vibration free mounting using the integral
mounting holes.
Do not mount flammable material close to the E3 drive.
Ensure that the minimum cooling air gaps, as detailed in section
3.4. Guidelines for mounting on page 8
.
Ensure that the ambient temperature range does not exceed the permissible limits for the E3 drive given in section
.
3.2. UL Compliant Installation
Refer to section
10.5. Additional Information for UL Compliance on page 55
for Additional Information for UL Compliance.
3.3. Mechanical Dimensions
C
Drive Size
A
B
C
D
E
Weight
mm
in
mm
in
mm
in
mm
in
mm
in
kg
Ib
1
232
9.13
161
6.34
162
6.37
189
7.44
148.5
5.85
2.3
5
2
257
10.12
188
7.4
182
7.16
200
7.87
178
7.00
3.5
7.7
3
310
12.2
211
8.3
235
9.25
252
9.92
197
7.75
6.6
14.5
4
360
14.17
240
9.44
271
10.67
300
11.81
227
8.94
9.5
20.9
Mounting Bolts
Tightening Torques
Frame Size
Metric
UNF
Frame Size
Required Torque
Terminal Type
All Sizes
M4
#8
Control Terminals
All
0.5 Nm
4.5lb-in
Rising Clamp
Power Terminals
1 - 3
0.8 Nm
7 lb-in
Rising Clamp
4
2 Nm
18 lb-in
Rising Clamp