NOTE If a charge problem is determined (high or
low):
A. Check for possible refrigerant leaks.
B. Recover all remaining refrigerant from unit and
repair leak.
C. Evacuate unit down to 29" of vacuum
D. Recharge the unit with refrigerant by weight.
This is the only way to ensure a proper charge.
12. For iSeries Smart Actuator and water valve
installation, refer to the
Valve and Actuator
Installation/Removal
section on page 31.
13. It is advised to rotate the manual operation button,
located on the top of the iSeries Smart Actuator,
several times to make sure the water valve is loose
and not seized before operation. This simple step
will provide assurance the 3-way water valve is free
to move once power is applied.
IMPORTANT
Operator must be removed from the valve
body and ball valve must be in the full
open position before soldering. Valve is
shipped in the full closed position.
FIGURE 35
Water Temperature and Pressure Procedure
10
120
110
100
90
80
70
60
50
40
30
20
0
Retaining cap, hand tighten only
Pete's test plug
Test plug cap
Barbed 90° adapter
MIS-2622 A
NOTE: Slide retaining cap back to expose
double o-rings. Apply petroleum jelly to o-rings
to prevent damage and aid in insertion
with guage adaptor
Dial face pressure guage
Thermometer