Manual 2100-738C
Page
34 of 73
MIS-3009A
Adjustments
17
12
FULLY OPEN
1500
20
16
1450
19
15
1400
18
14
1350
17
12
1300
16
11
1250
15
10
1200
14
9
1150
13
8
1100
MIS-3009 A
4-20mA AN (ppm)
Damper (1)
Approc. Blade
Position (2)
4
700
FULLY CLOSED
0
5
750
1
6
800
2
7
850
3
8
900
4
9
950
5
10
1000
6
11
1050
7
Settings Recommended
Default
RON
Not Used
ROF
Not Used
DSP
C
CT
UNI
US
US
COL
700
0
COH
1500
2000
TOL
Not Used
TOH
Not Used
BAR See Instrution with Controller
For High Altitude Installations
CAL
Used for Field Calibration
(1) Damper should be fully closed at 700 ppm, if not Potentiometer R7 can be adjusted
clockwise (CW) to close it. If it is fully closed at 700 ppm or lower no adjustments required.
(2) Blade as referenced to the Blade Position Label.
PRESS UP AND DOWN
ARROWS TO ENTER
CONFIGURATION MODE
USE ARROWS TO SELECT
SETTING. PUSH MIDDLE
BUTTON TO CHANGE.
CONTROLLER WILL
SHOW SET.
FOR PROPER OPERATION
POSITIONED AS SHOWN
JUMPERS MUST BE
NOTE: MENU
JUMPER MUST
BE SET TO "ON"
TO CHANGE ANY
SETTINGS WITH
THE FRONT BUTTONS.
TO LOCK THE CO2
CONTROLLER MOVE
JUMPER TO "OFF" AFTER
IT HAS BEEN CONFIGURED
FIGURE 26
CO
2
Control Configuration