Manual 2100-738C
Page
53 of 73
Inputs to the Board
Outputs from the Board
Energize on Unit
Terminal Strip
Mode
Occupied/
Unoccupied
RAT Y B W2 A1 D G G1 BK RV TWV W YO A2
G
Blower
Unoccupied
X
X
X
G, A
Blower
Occupied
X
X
X
X
X
Y1, O, G
Part Load Cooling
Unoccupied
X
X
X
X
X
Y1, O, G, A
Part Load Cooling
Occupied
X
X
X
X
X
X
X
Y1, O, G, D
Part Load Cooling/Dehum
Unoccupied
X
X X
X
X
Y1, O, G, D, A
Part Load Cooling/Dehum
Occupied
X
X
X X
X
X
X
Y1, Y2, O, G,
Full load Cooling
Unoccupied
X
X
X
X
X
Y1, Y2, O, G, A
Full load Cooling
Occupied
X
X
X
X
X
X
X
Y1, O, G, D
Full Load Cooling/Dehum
Unoccupied
X
X X
X
X
Y1,G, O, D, A
Full Load Cooling/Dehum
Occupied
X
X
X X
X
X
X
Y1, G
Part Load Heat Pump
Unoccupied
X
X
X
X
X
Y1, G, A
Part Load Heat pump
Occupied
X
X
X
X
X
X
X
Y1, G, D
Part Load Heat Pump/Dehum
Unoccupied
X
X X
X
X
Y1, G, D, A
Part Load Heat Pump/Dehum
Occupied
X
X
X X
X
X
X
Y1, Y2, G
Full Load Heat Pump
Unoccupied
X
X
X
X
X
Y1, Y2, G, A
Full Load Heat Pump
Occupied
X
X
X
X
X
X
X
Y1, Y2, G, D
Full Load Heat Pump/Dehum
Unoccupied
X
X X
X
X
Y1, Y2, G, D, A
Full Load Heat Pump/Dehum
Occupied
X
X
X X
X
X
X
Y1, Y2, G, W2
Part Load Heat Pump w/Aux. Heat
Unoccupied
X
X
X
X
X
X
X
Y1, Y2, G, W2
Part Load Heat Pump w/Aux. Heat
Occupied
X
X
X
X
X
X
X
X
X
Y1, Y2, G, W2, D
Part Load Heat Pump w/Aux. Heat/
Dehum
Unoccupied
X
X
X X
X
X
X
Y1, Y2, G, W2 D, A
Part Load Heat Pump w/Aux. Heat/
Dehum
Occupied
X
X
X
X X
X
X
X
X
G, W2
Aux. Heat
Unoccupied
X
X
X
X
X
G, W2, A
Aux. Heat
Occupied
X
X
X
X
X
X
G, W2, D
Aux. Heat/Dehum
Unoccupied
X
X X
X
X
X
G, W2, D, A
Aux. Heat/Dehum
Occupied
X
X
X X
X
X
X
X
D
Dehumidifiction
Unoccupied
X
X
X
X
D, A
Dehumidifiction
Occupied
X
X
X
X
X
X
Energize on Unit
Terminal Strip
Mode
Occupied/
Unoccupied
RAT Y B W2 A1 D G G1 BK RV TWV W YO A2
Inputs to the Board
Outputs from the Board
Table 11
Dehumidification Relay Logic Board
NOTES
1. Cooling takes precedence over dehumidification. A cooling call cancels dehumidification.
2. For dehumidification, the "O" (reversing valve) is activated through the dehumidification cube relay.