Manual 2100-738C
Page
73 of 73
The
following
information
is
needed
to
verify
performance
of
the
system.
Note:
Before
testing,
disable
desuperheater,
auxiliary
electric
heat,
and
any
ventilation
equipment
that
may
allow
outdoor
air
into
the
system.
Measurements
should
be
taken
after
a
minimum
10
min.
run
time
to
ensure
“steady
‐
state”
of
operation.
Temperature
and
pressure
measurements
should
be
taken
with
a
single
thermometer
and
pressure
gauge
to
eliminate
discrepancies
between
multiple
devices.
Fluid
Data:
1
st
Stg.
Cool
2
nd
Stg.
Cool
1
st
Stg.
Heat
2
nd
Stg.
Heat
5. Entering
Fluid
Temperature
°F
__________
__________
__________
__________
6. Leaving
Fluid
Temperature
°F
__________
__________
__________
__________
7. Entering
Fluid
Pressure
psi
__________
__________
__________
__________
8. Leaving
Fluid
Pressure
psi
__________
__________
__________
__________
9. Pressure
Drop
t
hrough
c
oil
(psi)
__________
__________
__________
__________
Using
the
specific
model
number
and
pressure
drop,
refer
to
Water
Coil
Pressure
Drop
Chart
on
page
6
to
find
gallons
‐
per
‐
minute
flow
through
water
coil.
10. GPM
through
coil
__________
__________
__________
__________
Air
Data:
1
st
Stg.
Cool
2
nd
Stg.
Cool
1
st
Stg.
Heat
2
nd
Stg.
Heat
11. Dry
Bulb
Return
Air
Temp
°F
__________
__________
__________
__________
12. Wet
Bul
b
Return
Air
Temp
°F
__________
__________
__________
__________
13. Dry
Bulb
Supply
Temperature
°F
__________
__________
__________
__________
14. Wet
Bulb
Supply
Air
Temp
°F
__________
__________
__________
__________
15. Return
Static
Pressure
“WC
__________
__________
__________
__________
16. Supply
Static
Pressure
“WC
__________
__________
__________
__________
Refrigerant
Data:
1
st
Stg.
Cool
2
nd
Stg.
Cool
1
st
Stg.
Heat
2
nd
Stg.
Heat
17. Head
Pressure
psi
__________
__________
__________
__________
18. Suction
Pressure
psi
__________
__________
__________
__________
19. Liquid
Line
Temperature
°F
__________
__________
__________
__________
Note:
L
iquid
line
temperature
should
be
measure
directly
before
metering
device.
20. Suction
Line
Temperature
°F
__________
__________
__________
__________
Note:
S
uction
line
temperature
should
be
measured
approximately
6”
from
compressor.
Calculate
the
subcooling
from
line
#17
and
Line
#19
(Typically
10°F
to
30°F)
21. Coil
Subcooling
°F
__________
__________
__________
__________
Calculate
the
superheat
from
line
#18
and
Line
#20
(Typically
6°F
to
12°F)
22. Coil
Superheat
°F
__________
__________
__________
__________
Electrical
Data:_
1
st
Stg.
Cool
2
nd
Stg.
Cool
1
st
Stg.
Heat
2
nd
Stg.
Heat
23. Voltage
at
Load
Side
of
Contactor
__________
__________
__________
__________
Note:
Voltage
must
be
within
197VAC
to
253VAC
(for
208V/230V),
414VAC
to
506VAC
(for
460V)
24. Amperage
Draw
of
Compressor
__________
__________
__________
__________
25. Amperage
Draw
of
Blower
Motor
__________
__________
__________
__________
Note:
consult
Electrical
Table
on
page
5
to
compare
against
typical
run
load
amps.
Note: Consult Electrical Specifications tables on page 8 to compare against typical run load amps.