Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric
Code (latest revision), article 310 for power conductor sizing.
l
Based on 75ºC copper wire. All wiring must conform to the National Electric Code and all local codes.
Model
RATED VOLTS,
Hz & PHASE
NO. FIELD
POWER
CIRCUITS
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM
EXTERNAL FUSE
OR CIRCUIT
BREAKER
FIELD POWER
WIRE SIZE
l
GROUND
WIRE SIZE
l
QW2S3DA0Z
QW2S3DB0Z
QW2S3DC0Z
230/208-60-1
230/208-60-3
460-60-3
1
1
1
20
14
9
30
20
15
10
12
14
10
12
14
QW3S3DA0Z
QW3S3DB0Z
QW3S3DC0Z
230/208-60-1
230/208-60-3
460-60-3
1
1
1
27
22
13
40
30
15
8
10
14
10
10
14
QW4S3DA0Z
QW4S3DB0Z
QW4S3DC0Z
230/208-60-1
230/208-60-3
460-60-3
1
1
1
37
28
17
50
35
20
8
8
12
10
10
12
QW5S3DA0Z
QW5S3DB0Z
QW5S3DC0Z
230/208-60-1
230/208-60-3
460-60-3
1
1
1
43
30
15
60
40
20
8
8
10
10
10
10
TABLE 1B
Electrical Specifications