Remote Indoor Temperature/Humidity
Sensor Orientation
Current versions of the remote indoor temperature/
humidity sensor need to be installed with the shielded
cable wires entering the bottom of the back of the
sensor to connect to the sensor terminals (see Figure
50). Earlier versions of this sensor were installed so
that the sensor wires entered through the top of the
back of the sensor (see Figure 51).
The orientation
of the sensor affects the position of the DP1/DP2
jumpers. Depending on how the sensor is installed,
be sure to confirm that the jumpers are in the proper
position for the 0-1 V setting as shown in the figures
below.
This applies to all indoor temperature/humidity
sensors connected to the LC controller.
See illustration
mounted inside of sensor cover for further detail on
jumper position.
DP1
DP2
DP1
DP2
Jumper
FIGURE 50
Current Sensor Orientation
(Shielded Cable Wires Enter from Bottom)
FIGURE 51
Earlier Sensor Orientation
(Shielded Cable Wires Enter from Top)
Jumper
DP1 and DP2 Jumpers
Positioned for 0-1V
(Current Orientation)
DP1 and DP2 Jumpers
Positioned for 0-1V
(Earlier Orientation)
Summary of Contents for MEGA-TEC W090A
Page 2: ......
Page 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Page 60: ...Manual 2100 671C Page 58 of 59...
Page 61: ...Manual 2100 671C Page 59 of 59...
Page 62: ......
Page 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 118: ......
Page 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Page 149: ......
Page 157: ......