Manual 2100-671C
Page
23 of 59
Discharge/Liquid Pressure Transducer Alarm
When the discharge pressure sensor value is out of
range (0-650 PSIG), the controller will generate a
sensor failure alarm to indicate the sensor is not
working properly.
This alarm is fixed and cannot be adjusted.
Liquid Temperature Sensor
The unit is equipped with a liquid line temperature
sensor to monitor the temperature of the liquid
refrigerant leaving the condenser and entering the EEV.
The temperature is measured with a 10k ohm NTC
thermistor.
The liquid temperature sensor can be verified and
adjusted by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to
I/O Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Analog Inputs
;
press ENTER key.
5. Press UP or DOWN keys to scroll to
Analog Ins
16/19
(for circuit 1) or
Analog Ins 17/19
(for
circuit 2).
6. Reference the
Value
to verify the temperature (see
Figure 31).
7. If an offset needs to be applied, press ENTER key
to scroll to
Offset
.
8. Press UP or DOWN keys to change the offset to
desired value.
9. Press ENTER key to save.
10. Press ESCAPE key several times to return to Main
Menu screen.
FIGURE 31
Adjusting Discharge/Liquid Temperature Input
Outdoor Temperature Sensor
The unit is equipped with a combination outdoor
temperature and humidity sensor. The temperature is
measured with a 10k ohm NTC thermistor. See page
27 for more information.
Condenser Fan Operation
Condenser Fan Speed Control
The fan will speed up or slow down to attempt to
maintain a discharge pressure setpoint. Because the
control is dependent on the discharge pressure sensor,
the controller will alter its operation if the sensor is not
enabled or failed. When the liquid pressure transducer
is not enabled or considered failed by the controller, a
nominal speed will be used during a compressor call
(see Table 9).
TABLE 9
Condenser Fan Nominal Speed
Unit
Discharge Pressure
Setpoint
Nominal
Speed
W090A
390 psig
60%
W120A
420 psig
74%
W150A
410 psig
70%
Compressor
Compressor Components
Compressor
Three Phase Scroll Compressor Start Up Information
Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction. Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.
However, three phase compressors will rotate in either
direction depending upon phasing of the power.
Since there is a 50-50 chance of connecting power
in such a way as to cause rotation in the reverse
direction, verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as substantially
reduced current draw compared to tabulated values.
Verification of
proper rotation
must be made at the time
the equipment is put into service. If improper rotation
is corrected at this time, there will be no negative
impact on the durability of the compressor. However,
reverse operation for over 1 hour may have a negative
impact on the bearing due to oil pump out.
Summary of Contents for MEGA-TEC W090A
Page 2: ......
Page 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Page 60: ...Manual 2100 671C Page 58 of 59...
Page 61: ...Manual 2100 671C Page 59 of 59...
Page 62: ......
Page 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 118: ......
Page 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Page 149: ......
Page 157: ......