6. Verify the measurement displayed on screen is
accurate (see Figure 29).
7. If the measurement needs to be adjusted, apply an
offset value by pressing the ENTER key to scroll to
Offset
.
8. Press UP or DOWN keys to adjust the offset. The
update will not take effect until the cursor is
moved out of the offset parameter.
9. Once adjusted, the ESCAPE key several times to
return to Main Menu screen.
FIGURE 30
Voltage to Pressure:
Discharge/Liquid Pressure Transducer
Voltage Offset
Troubleshooting the Discharge/Liquid Pressure
Transducer
0-650 psig
.5 to 4.5v
4.5-.5 + 4 volt range/650 psig = .00615 volts per 1 psig
Example:
325 psig x .00615 + .5 v = 2.5 volts
Formula for Tech:
Measured Pressure x .00615 + Voltage Offset =
Expected Transducer Signal Voltage (see Figure 30).
FIGURE 29
Adjusting Discharge/Liquid Transducer
Pressure Values
FIGURE 28
Enabling Fan Override
4. Press UP or DOWN keys to scroll to
Fans / Blowers
;
press ENTER key.
5. Press UP or DOWN keys to scroll to
Condenser Fan
1
(see Figure 28).
6. Press ENTER key to scroll to the
Fan Overrides?
7. Press UP or DOWN keys to change the value from
No
to
Go
. The override will begin and the screen
will change to the override screen (see Figure 28).
The override will last for 5 minutes or until the
Fan
Overrides
parameter is set to
No
again.
Liquid Pressure Sensor
The unit has a pressure transducer installed on the liquid
line between the condenser and electronic expansion
valve (EEV). The transducer is used for condenser fan
speed control and for monitoring of system operation.
The liquid line transducer is also referred to as the
discharge or liquid pressure sensor.
The discharge/liquid pressure sensor input can be
verified and adjusted by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to
I/O Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Analog Inputs
;
press ENTER key.
5. Press UP or DOWN keys to scroll to
Analog Ins 7/19
(for circuit 1) or
Analog Ins 9/19
(for circuit 2).
Summary of Contents for MEGA-TEC W090A
Page 2: ......
Page 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Page 60: ...Manual 2100 671C Page 58 of 59...
Page 61: ...Manual 2100 671C Page 59 of 59...
Page 62: ......
Page 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 118: ......
Page 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Page 149: ......
Page 157: ......