Manual 2100-671C
Page
30 of 59
7. To apply an offset, press ENTER key to scroll to
Offset
.
8. Press UP or DOWN keys to change to the desired
value.
9. Press ENTER key to save the value.
High Mixed Air Temperature Alarm
To keep the economizer from bringing in air that is too
warm, an alarm will be generated when the mixed air is
2° above the return air temperature for 300 seconds.
This alarm will not be generated if the mixed air
temperature sensor has failed. The alarm can only be
activated during a free cooling call. The alarm is a user
reset and must be cleared by the end user.
Low Mixed Air Temperature Alarm
To keep the economizer from bringing in air that is too
cold, an alarm will be generated when the mixed air
temperature is 5°F below the mixed air temperature
control setpoint for 300 seconds. If this alarm is active,
the economizer will be disabled for the current cooling
call. This alarm will reference the mixed air temperature
control setpoint to ensure that when the mixed air setpoint
changes, the alarm dynamically changes with it. This
alarm will not be generated if the mixed air temperature
sensor has failed. The alarm can only be activated during
a free cooling call and requires a user reset.
Economizer Operation
See Figure 67 on page 56 for ventilation airflow paths.
The economizer has four types of operation. The
first mode is "None" where the economizer is never
utilized, except for emergency purposes. The second
mode is "Dry Bulb" where the outdoor temperature is
the only consideration for economizer use on a free
cooling call. The third mode is "TempHum" where the
outdoor temperature and humidity are considered
for economizer use on a free cooling call. The fourth
mode is "Enthalpy" where the outdoor temperature,
humidity and calculated dew point are considered for
economizer operation on a free cooling call.
FIGURE 41
Mixed Air Temperature Sensor
To change the economizer type:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
System Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Economizer
Setup A2
; press ENTER key.
5. Press ENTER key to scroll to
Type
(see Figure 42).
6. Press UP or DOWN keys to change the
Type
desired
value to
None
,
Dry Bulb
,
TempHum
or
Enthalpy
.
7. Press ENTER key to save the value and scroll to
the next parameter.
NOTE:
The following parameters are for the
temperature consideration for economizer use.
Applies to
Dry Bulb
,
TempHum
and
Enthalpy
type.
8. The cursor should now be on the
Mixed Air Tamp
parameter.
9. Press UP or DOWN keys to change the parameter
to the desired value.
10. Press ENTER key to save the value and scroll to
the next parameter.
11. The cursor should now be on
Delay
parameter.
12. Press UP or DOWN keys to change the parameter
to the desired value.
13. Press ENTER key to save the value and move to
the next parameter.
14. The cursor is now on the
Min Position
parameter.
15. Press UP or DOWN keys to change the parameter
to the desired value (see
Economizer Operation −
Minimum Position
on page 32 for more information).
16. Press ENTER key to save the value.
17. Press the DOWN key to navigate to the
A3
screen.
NOTE:
The
A3
screen will not display if economizer
mode is set to
None
. Also, the contents of the
screen will change depending on which type is
FIGURE 42
Economizer Setup
Summary of Contents for MEGA-TEC W090A
Page 2: ......
Page 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Page 60: ...Manual 2100 671C Page 58 of 59...
Page 61: ...Manual 2100 671C Page 59 of 59...
Page 62: ......
Page 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 118: ......
Page 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Page 149: ......
Page 157: ......