7960-788
Revised: 2-13-17
Commissioning Report
Page 2 of 3
Yes No Are EMI filters installed on the 2 wire shielded cable ran from the controller to the
units?
Yes No
A continuity check between the 2 communications wires with a multimeter will verify
proper “+” and “-“connections have been made for the 2 wire shielded cable. This may
be checked at the unit or controller. No continuity should be observed. If continuity is
observed, check communications wire “+” and “-“connections for reversal. Has a
continuity check been performed with a multimeter?
HVAC Unit #1 Setup – Verify the following:
Yes No Is unit addressed as #1 using the TEC-EYE service tool?
Yes No Indoor blower, economizer, compressor, condenser fan, electric heat is operational?
High Pressure (psi) measurement from TEC-EYE service tool.
Low Pressure (psi) measurement from TEC-EYE service tool.
Measure Voltage at unit circuit breaker with Multimeter. If power is below 220 Volts,
disconnect power and move red wire on low voltage transformer to 208V terminal.
HVAC Unit #2 Setup – Verify the following:
Yes No Is unit addressed as #2 using the TEC-EYE service tool?
Yes No Indoor blower, economizer, compressor, condenser fan, electric heat is operational?
High Pressure (psi) measurement from TEC-EYE service tool.
Low Pressure (psi) measurement from TEC-EYE service tool.
Measure Voltage at unit circuit breaker with Multimeter. If power is below 220 Volts,
disconnect power and move red wire on low voltage transformer to 208V terminal.
HVAC Unit #3 Setup – Verify the following:
Yes No Is unit addressed as #3 using the TEC-EYE service tool?
Yes No Indoor blower, economizer, compressor, condenser fan, electric heat is operational?
High Pressure (psi) measurement from TEC-EYE service tool.
Low Pressure (psi) measurement from TEC-EYE service tool.
Measure Voltage at unit circuit breaker with Multimeter. If power is below 220 Volts,
disconnect power and move red wire on low voltage transformer to 208V terminal.
HVAC Unit #4 Setup – Verify the following:
Yes No Is unit addressed as #4 using the TEC-EYE service tool?
Yes No Indoor blower, economizer, compressor, condenser fan, electric heat is operational?
High Pressure (psi) measurement from TEC-EYE service tool.
Low Pressure (psi) measurement from TEC-EYE service tool.
Measure Voltage at unit circuit breaker with Multimeter. If power is below 220 Volts,
disconnect power and move red wire on low voltage transformer to 208V terminal.
Jobsite Temperature Measurements – Record the following:
Summary of Contents for MEGA-TEC W090A
Page 2: ......
Page 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Page 60: ...Manual 2100 671C Page 58 of 59...
Page 61: ...Manual 2100 671C Page 59 of 59...
Page 62: ......
Page 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 118: ......
Page 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Page 149: ......
Page 157: ......