Manual 2100-671C
Page
21 of 59
3. Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to
Blower Config
A10
screen.
5. Press ENTER key to scroll to
Balanced Climate
or
High Sensible
parameter (see Figure 27).
6. Press UP or DOWN key to change value from
Off
to
On
or
On
to
Off
.
The unit will automatically switch to the required
speed for each mode. For more information on the
high sensible command from LC, please see LC6000
Service Instructions 2100-669.
Additional Indoor Airflow Alarms
Supply Air Temperature Alarm
When the supply air temperature sensor value is out of
range (-41.0 to 303.0°F), the controller will generate
a sensor failure alarm to indicate the sensor is not
working properly.
This alarm is fixed and cannot be adjusted.
Condenser Fan
Condenser Fan Components
Condenser Fan
The unit is equipped with a condenser fan that is driven
by an electronically commutated motor (ECM). This
fan is controlled by a 0-100% command using modbus
serial communication. The fan operates between 100-
1200 rpm.
To enable fan override:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to
I/O Config
;
press ENTER key.
FIGURE 27
Enabling/Disabling High Sensible Operation or
Balanced Climate Operation
TABLE 8
Blower Speed Settings*
Mode
Unit
W090
W120
W150
Free Cooling
45%
57%
65%
Cooling Stage 1
High Sensible
38.5%
48.5%
54%
Nominal
33%
42%
47%
Balanced Climate
27.6%
32.6%
36.4%
Cooling Stage 2
High Sensible
52%
63%
83%
Nominal
45%
57%
65%
Balanced Climate
36.4%
43.8%
50.5%
Cooling Stage 3
High Sensible
52%
63%
83%
Nominal
45%
57%
65%
Balanced Climate
36.4%
43.8%
50.5%
Heating Stage 1
57%
57%
57%
Heating Stage 2
57%
57%
57%
Emergency Ventilation
100%
100%
100%
Freeze Alarm
80%
80%
80%
Dehumidification
57%
57%
57%
* Blower position percentages are communicated through Modbus and cannot be verified with meter.
Summary of Contents for MEGA-TEC W090A
Page 2: ......
Page 59: ...Manual 2100 671C Page 57 of 59 I O Layout...
Page 60: ...Manual 2100 671C Page 58 of 59...
Page 61: ...Manual 2100 671C Page 59 of 59...
Page 62: ......
Page 111: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 112: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 118: ......
Page 122: ...Manual 2110 1451D Page 4 of 28 ECONOMIZER INTAKE HOODS 7 2 4 5 6 8 3 1 4 SEXP 899...
Page 149: ......
Page 157: ......