Manual 2100-704C
Page
46 of 47
TABLE 6
WR Series Wall-Mount Unit Status Messages
Message
Description
Waiting...
PLC is on and has not started
running the application yet.
Orphan Mode
Unit is on and in orphan mode with
no calls for heating or cooling.
LC Online
Unit is on and communicating with
the LC6000 with no heating or
cooling calls.
Cont. Blower
Unit is operating with continuous
blower when no heating or cooling
calls are present.
Power Loss
Unit has experienced a loss of main
utility power. Alarm only available
with inverter units.
Freecooling
Unit is actively economizing.
Optimized Cool
Unit is mechanical cooling while
actively economizing.
Cooling
Unit is actively mechanical cooling.
Heating
Unit is actively heating.
Passive Dehum
Unit is taking measures to decrease
humidity without using extra energy.
Active Dehum
Unit is taking active measures to
decrease humidity.
Self Test
Unit is performing a self test.
Off by Alarm
Unit has major fault preventing
operation.
Off by DI
Unit is disabled by the local unit
disable/smoke input.
Off by LC
Unit has been turned off by the
supervisory controller.
Off by Keyboard
Unit has been turned off by the
local user.
Override Active
There is an active override on the
system.
Emergency Vent
Unit is in Emergency Ventilation.
LC6000 has an active hydrogen
alarm.
Emergency Cool
Unit is in Emergency Cooling.
Indoor temperatures have exceeded
high temp alarms.
Emergency Off
Unit is in Emergency Off. LC6000
has an active smoke alarm.
TABLE 7
LC6000 Status Messages
Message
Description
On
The LC6000 is ready and functioning
properly.
Off by BMS
The LC6000 is being turned off by the
Building Management System through
Modbus TCP/IP.
Off by
Keyboard
The LC6000 is turned off using the
(D. On/Off) Menu on the PGD. All
communicating units will be inactive.
Comfort
Mode
The LC6000 is set to Comfort Mode.
This mode is used to temporarily override
heating/cooling setpoints and maintain
a default temperature of 72°F for 60
minutes.
Emergency
Cooling
A high temperature has been sensed in
one or more zones. All available units
in that zone are sent a command for
emergency cooling. (Refer to unit manual
for emergency cooling sequence.)
Emergency
Vent
Input signal from an external device at
terminal DI2 (e.g., hydrogen detector).
Units that are equipped with a ventilation
option and configured will open the
dampers at 100% with the blower at full
speed.
Summary of Contents for FUSION-TEC WR Series
Page 2: ......
Page 50: ......
Page 53: ......
Page 63: ......
Page 69: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 70: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 75: ......
Page 80: ...Manual 2110 1547E Page 5 of 20 This page intentionally left blank...
Page 84: ...Manual 2110 1547E Page 9 of 20 This page intentionally left blank...
Page 96: ......
Page 100: ......