Commissioning Report
Page 2 of 3
Yes No Are EMI filters installed on the 2 wire shielded cable ran from the controller to the
units?
Yes No
A continuity check between the 2 communications wires with a multimeter will verify
proper “+” and “-“connections have been made for the 2 wire shielded cable. This may
be checked at the unit or controller. No continuity should be observed. If continuity is
observed, check communications wire “+” and “-“connections for reversal. Has a
continuity check been performed with a multimeter?
HVAC Unit #1 Setup – Verify the following:
Yes No Is unit addressed as #1 using the TEC-EYE service tool?
Yes No Indoor blower, economizer, compressor, condenser fan, electric heat is operational?
High Pressure (psi) measurement from TEC-EYE service tool.
Low Pressure (psi) measurement from TEC-EYE service tool.
Measure Voltage at unit circuit breaker with Multimeter. If power is below 220 Volts,
disconnect power and move red wire on low voltage transformer to 208V terminal.
HVAC Unit #2 Setup – Verify the following:
Yes No Is unit addressed as #2 using the TEC-EYE service tool?
Yes No Indoor blower, economizer, compressor, condenser fan, electric heat is operational?
High Pressure (psi) measurement from TEC-EYE service tool.
Low Pressure (psi) measurement from TEC-EYE service tool.
Measure Voltage at unit circuit breaker with Multimeter. If power is below 220 Volts,
disconnect power and move red wire on low voltage transformer to 208V terminal.
HVAC Unit #3 Setup – Verify the following:
Yes No Is unit addressed as #3 using the TEC-EYE service tool?
Yes No Indoor blower, economizer, compressor, condenser fan, electric heat is operational?
High Pressure (psi) measurement from TEC-EYE service tool.
Low Pressure (psi) measurement from TEC-EYE service tool.
Measure Voltage at unit circuit breaker with Multimeter. If power is below 220 Volts,
disconnect power and move red wire on low voltage transformer to 208V terminal.
HVAC Unit #4 Setup – Verify the following:
Yes No Is unit addressed as #4 using the TEC-EYE service tool?
Yes No Indoor blower, economizer, compressor, condenser fan, electric heat is operational?
High Pressure (psi) measurement from TEC-EYE service tool.
Low Pressure (psi) measurement from TEC-EYE service tool.
Measure Voltage at unit circuit breaker with Multimeter. If power is below 220 Volts,
disconnect power and move red wire on low voltage transformer to 208V terminal.
Jobsite Temperature Measurements – Record the following:
Summary of Contents for FUSION-TEC WR Series
Page 2: ......
Page 50: ......
Page 53: ......
Page 63: ......
Page 69: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 70: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 75: ......
Page 80: ...Manual 2110 1547E Page 5 of 20 This page intentionally left blank...
Page 84: ...Manual 2110 1547E Page 9 of 20 This page intentionally left blank...
Page 96: ......
Page 100: ......