Manual 2100-704C
Page
45 of 47
Menu Screens and Password Levels
WR Series Unit
System Config: A1-A10 User (2000)
Adv. System Config: B1-B8 Technician (1313)
I/O Config: C1-C15 Technician (1313)
On/Off: User (2000)
Alarm Logs: User (2000)
Settings
Date/Time: Technician (1313)
Language: User (2000)
Import/Export
Unit Parameters: Engineer (9254)
Alarm Log Export: User (2000)
7 Day Log Export: User (2000)
Initialization
Alarm Management: User (2000)
System Default: Engineer (9254)
Change
Passwords
Logout: Used to log out of the current password
level. Entering back into the menu requires
password.
LC1000 Controller
System Config
General: User (2000)
Zone 1: User (2000)
Zone 2: User (2000)
Zone 3: User (2000)
Adv. System Config: B1-B13 Technician (1313)
I/O Configuration: C1-C10 Technician (1313)
On/Off: User (2000)
Alarm Log: User (2000)
Settings
Date/Time: Technician (1313)
Language: User (2000)
Network Config: Technician (1313)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Restart:
User
(2000)
Parameter Config: Engineer (9254)
Alarm Export: User (2000)
Logout: Used to log out of the current password
level. Entering back into the menu requires
password.
ADDITIONAL INFORMATION
Setpoints
The
LC6000
setpoints will determine the cooling and
heating setpoints when
communicating with the wall-
mount units
. The
unit
cooling and heating setpoints
will determine the cooling and heating setpoints when
in orphan mode
.
If at any time the unit(s) loses communication with
the LC6000 controller, the unit(s) will go into orphan
mode.
Calibrating Sensors
1. Press MENU key on LC controller interface to go to
the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
I/O Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to sensor to be
adjusted.
5. Press ENTER key to scroll to
Offset
(see Figure
57).
6. Press UP or DOWN keys to add or subtract to the
sensor offset value.
7. Press ENTER key to save.
User
2000
Technician
1313
Engineer
9254
Use UP or DOWN keys and ENTER key to enter password
TABLE 5
LC6000/TEC-EYE Passwords (Defaults)
FIGURE 57
Adjusting Sensor Offset Value
Summary of Contents for FUSION-TEC WR Series
Page 2: ......
Page 50: ......
Page 53: ......
Page 63: ......
Page 69: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 70: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 75: ......
Page 80: ...Manual 2110 1547E Page 5 of 20 This page intentionally left blank...
Page 84: ...Manual 2110 1547E Page 9 of 20 This page intentionally left blank...
Page 96: ......
Page 100: ......