Supercedes:
NEW
Page 1 of 2
This quick start guide is designed to lead an installer
through the steps necessary for setting up a Bard air
conditioning system composed of FUSION-TEC WR Series
wall-mount units paired with an LC6000 controller. See
the latest versions of FUSION-TEC WR Series/LC6000
System Installation Instructions 2100-704, FUSION-
TEC WR Series Service Instructions 2100-688 and
LC6000 Service Instructions 2100-669 for more detailed
information on the installation, service and maintenance
of this Bard air conditioning system.
The TEC-EYE
TM
hand-held diagnostic tool and LC6000
controller will both be used in this installation. The TEC-
EYE diagnostic tool is shipped inside the controller and
a cable is included to connect it to the wall-mount unit
control board.
NOTE:
Each unit must have a unique address for the
communication to work properly. Bard also
recommends labeling each unit for ease in
identification.
8. Press ENTER key to scroll to
UOM
(unit of measure
)
.
9. If desired, press UP/DOWN keys to change the value
from
USA
to
SI
,
NC
,
LON
,
CAN
or
UK
. Units are
preconfigured for each selection.
10. Press ENTER key to scroll to
Zone
.
11. If desired, press UP/DOWN keys to change the value
to the desired zone (1, 2 or 3).
12. Press ENTER key to save.
Execute a run test on each unit to verify the equipment is
functioning correctly (TEC-EYE)
1. Use UP/DOWN keys to scroll to
Run Test A10
.
2. Press ENTER key to scroll to
Run Test Enable
parameter.
3. Use UP/DOWN key to change value to
ON
. The run
test will begin.
See most recent version of Installation Instructions
2100-704 if additional information on run testing units is
needed.
Clear unit alarm logs on each unit (TEC-EYE)
Units may have alarms logged due to testing. Unit alarm
logs must be cleared at time of installation. To clear the
wall-mount unit alarm logs:
1. Press MENU key to go to the Main Menu screen.
2. Use UP/DOWN/ENTER keys to enter password 1313.
3. Press UP/DOWN keys to scroll to
Settings
; press
ENTER key.
4. Press UP/DOWN keys to scroll to
Initialization
; press
ENTER key.
5. Press ENTER key to scroll to
Clear Alarm Logs?
.
6. Press UP/DOWN key to change value to
YES
; press
ENTER key.
After first unit has been set up and configured, follow the
above steps to set up and configure the remaining units.
The LC6000 controller will be used for the remaining
steps in the set-up process.
Set LC Controller Date/Time (LC Controller)
1. Press MENU key to access the Main Menu screen.
2. Use UP/DOWN/ENTER keys to enter password 1313.
3. Press the UP/DOWN keys to scroll to the
Settings
menu; press ENTER key.
4. Press UP/DOWN keys to scroll to
Date/Time
menu;
press ENTER key.
Manual: 2100-709
Date: 3-18-19
It is important to check the software version during
installation to ensure that the latest version has
been installed. Current software versions, change
log and installation instructions are available on
the Bard website at
http://www.bardhvac.com/
software-download/
NOTICE
SYSTEM SET-UP
Set up and configuration must be done to each FUSION-
TEC WR Series wall-mount unit using the TEC-EYE hand-
held diagnostic tool. Use the LC6000 controller for the
remaining steps.
IMPORTANT:
When working with circuit board
components, Bard recommends the use of
an anti-static wrist strap to prevent static
electricity shorts to electronic controls.
Address each wall unit and select unit zone and unit of
measure (TEC-EYE)
The address of the unit being looked at will be listed in
the upper right hand corner on the status screen. The
available addresses are 1-14.
1. Remove outer and inner unit control panel doors.
2. Connect TEC-EYE to wall-mount unit control board.
3. Press MENU key to access the Main Menu screen.
4. Press UP/DOWN/ENTER keys to enter password
1313.
5. Press UP/DOWN keys to scroll to
Sys Config
; press
ENTER key.
6. Press ENTER key to scroll to
Controller Address
.
7. Press UP/DOWN keys to change address to value
between 1 and 14.
Quick Start Guide
FUSION-TEC
®
WR Series/LC6000 Air Conditioning System
Summary of Contents for FUSION-TEC WR Series
Page 2: ......
Page 50: ......
Page 53: ......
Page 63: ......
Page 69: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 70: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 75: ......
Page 80: ...Manual 2110 1547E Page 5 of 20 This page intentionally left blank...
Page 84: ...Manual 2110 1547E Page 9 of 20 This page intentionally left blank...
Page 96: ......
Page 100: ......