Manual 2100-704C
Page
44 of 47
FIGURE 56
Clearing LC6000 Alarm Logs
To select economizer type for each zone:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter password 1313.
3) Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Zone 1
,
Zone 2
or
Zone 3
; press ENTER key.
5) Press UP or DOWN keys to scroll to
Zone FC
Settings A2-4
(Zone 1),
Zone FC Settings A3-4
(Zone 2) or
Zone FC Settings A4-4
(Zone 3
)
.
6) Press ENTER key to scroll to
Type
(see Figure
55).
7)
Press UP or DOWN keys to change economizer
type to
None
,
Drybulb
,
TempHum
or
Enthalpy
.
8) Press ENTER key to save.
FIGURE 55
Selecting Economizer Type
9. Clear Controller Alarm Logs
The LC6000 controller may have alarms logged
due to bench testing. Controller alarm logs must be
cleared at time of installation.
To clear the LC controller alarm logs:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press UP or DOWN keys to scroll to
Settings
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Initialization
; press ENTER key.
5) Press ENTER key to scroll to
Delete alarm
logs?
(see Figure 56).
6) Press UP or DOWN key to value to
YES
; press
ENTER key.
7) Press ESCAPE key several times to return to
Main Menu screen.
10. Complete Installation
Once all the installation steps have been
completed, all alarms and alarm logs have been
cleared and system verification and run test results
were satisfactory, the installation can now be
considered “complete".
Additional programming information can be found
in FUSION-TEC WR Series Service Instructions
2100-695 and LC6000 Service Instructions 2100-
669.
Summary of Contents for FUSION-TEC WR Series
Page 2: ......
Page 50: ......
Page 53: ......
Page 63: ......
Page 69: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Page 70: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Page 75: ......
Page 80: ...Manual 2110 1547E Page 5 of 20 This page intentionally left blank...
Page 84: ...Manual 2110 1547E Page 9 of 20 This page intentionally left blank...
Page 96: ......
Page 100: ......