FIGURE 31

Dust Sensor

Dust Sensor Failure Alarm

When the sensor reads a value that is outside of the 
acceptable 0 to 100% RH range, an alarm will be 
generated indicating the sensor has failed. This alarm 
is just a notification and will not disable any other 
features on the controller.
This alarm is fixed and cannot be adjusted.

Dust Limit Alarm

The controller has adjustable software setpoints 
(default to 80%) to indicate dust levels are too high 
and disable the economizer operation for 30 minutes. 
This alarm is not communicated to the NOC. Once 
the conditions are no longer present, the alarm will 
automatically clear.
To adjust the dust sensor alarm setpoint:
1.  Press MENU key to go to the Main Menu screen.
2.  Press UP or DOWN keys and ENTER key to enter 

USER password 2000.

3.  Press UP or DOWN keys to scroll to 

System Config

press ENTER key.

4.  Press UP or DOWN keys to scroll to 

Alarm Setup 

(A9)

; press ENTER key.

5.  Press ENTER key to scroll to 

Setpoint 

(see Figure 

32).

6.  Press UP or DOWN keys to change to the desired 

value.

7.  Press ENTER key to save the value.

NOTE: 

When the temperature outside is measured 

at or below 0°F, the dust sensor alarm will be 

disabled to allow economizer operation. This 

is done because the compressor is disabled 

below 0°F and the system would not have the 

capability to cool. 

Damper Blade

The system utilizes three damper blades used to bring 
in outdoor air and exhaust space air for economizer 
operation. The damper blades are made of sheet metal 
and are integrated into the equipment. 

Damper Switch

The economizer utilizes a magnetic switch to determine 
if the damper is operating correctly. This switch will be 
closed when the damper is closed and open when the 
damper is open.
To verify the status of the switch:
1.  Press MENU key to go to the Main Menu screen.
2.  Press UP or DOWN keys and ENTER key to enter 

TECHNICIAN password 1313.

3.  Press UP or DOWN keys to scroll to 

I/O Config

press ENTER key.

4.  Press UP or DOWN keys to scroll to 

Digital In 

Config (C2)

; press ENTER key.

5.  Reference the value located at 

6

 

Damp

 row and 

Val

 

column (see Figure 33).

6.  The input will display 

ON

 when the damper is 

closed (reflecting closed circuit on damper switch) 
and will display 

OFF

 when the damper is open 

(reflecting open circuit on damper switch).

FIGURE 32

Adjusting Dust Sensor Alarm Setpoint

FIGURE 33

Damper Switch

Summary of Contents for FUSION-TEC HR58APB

Page 1: ...bardhvac com Manual 2100 670 Supersedes NEW Date 6 2 17 NOTE LV1000 Controller is required for operation when multiple HR58AP units are used SERVICE INSTRUCTIONS FUSION TEC WALL MOUNT AIR CONDITIONER...

Page 2: ...flow Alarms 18 Supply Air Temperature Alarm 18 Condenser Fan 18 Condenser Fan Components 18 Condenser Fan 18 High Pressure Transducer 19 High Pressure Transducer Alarm 19 Discharge Temperature Sensor...

Page 3: ...itch Filter Indicator Light 16 Figure 20 Verifying Freeze Switch Status 17 Figure 21 Adjusting Freezestat Alarm Delay 18 Figure 22 Verifying Condenser Fan Output 18 Figure 23 Fan Blade Setting 18 Figu...

Page 4: ...on is made See Additional Publications for information on codes and standards Sizing of systems for proposed installation should be based on heat loss and heat gain calculations made according to meth...

Page 5: ...s to be limited to the most extreme situations DANGER signs should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved WARNING Indicate s a...

Page 6: ...n case of power failure The controller is designed to manage temperature levels to a user defined setpoint via control output signals to the wall mount air conditioning system The TEC EYE connects to...

Page 7: ...u is accessible from the Status screen Setpoints Information and Data Alarm Log are available through the Quick Menu Pressing the UP or DOWN keys while on the Status screen will change the Quick Menu...

Page 8: ...and program version information Data Alarm Log The alarm log screens show a log of each alarm There will be a log for when alarm occurred and if the alarm auto clears it will show when the alarm clea...

Page 9: ...n each wall mount unit In stand alone mode the wall unit uses a continuous blower setting to circulate room air into the return air inlet and uses the return air temperature sensor to control room tem...

Page 10: ...trol will compare the space temperature to the space setpoint Based on how far away from the setpoint the temperature is the loop will output a cooling or heating capacity number between 0 and 100 The...

Page 11: ...zer operation so there are a total of 2 cooling stages see Figure 9 Heating The unit is equipped with 1 stage of electric heat see Figure 10 Staging The unit will stage the cooling components based on...

Page 12: ...l to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Suction Pr Sensor C11 press ENTER key 5 Verify the measurement displayed on screen is accurate see Figure 11 6 If the measurement n...

Page 13: ...the valve NOTE The unit must be off to perform this override 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN...

Page 14: ...the condition is no longer present This alarm cannot be adjusted Indoor Airflow Indoor Airflow Components Blower The unit is equipped with a blower that is driven by an electronically commutated moto...

Page 15: ...or DOWN keys to change to the desired value 7 Press ENTER key to save the value FIGURE 17 Dirty Filter Switch and Blower Status Switch FIGURE 16 Adjusting Air Flow Alarm Delay Differential Airflow Sw...

Page 16: ...tubing routed to the blower and vent areas of the unit The switch circuit consists of a normally open filter pressure switch The switch will open when the pressure differential goes above the setting...

Page 17: ...he evaporator coil To prevent the coil from freezing and potentially allowing liquid refrigerant from the evaporator to enter the compressor the switch will open when the temperature at this sensor is...

Page 18: ...ween 100 1200 rpm To view the output of the condenser fan 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys...

Page 19: ...arm When the high pressure transducer sensor value is out of range 0 650 PSIG the controller will generate a sensor failure alarm to indicate the sensor is not working properly This alarm is fixed and...

Page 20: ...ed moving as little air as possible If the discharge pressure continues to go down to 250 PSI the condenser fan will turn off The fan will remain off with the compressor running until the pressure rea...

Page 21: ...operation The monitoring device protects the unit against compressor contactor chatter and reverse compressor rotation during these situations Compressor protection device has an adjustable 30 second...

Page 22: ...can be changed by 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys to scroll to Adv System Config press EN...

Page 23: ...new override value and the damper will travel to that position NOTE This override will last for 5 minutes or until the Override is changed back to Disabled Dust Sensor The unit has a dust sensor insta...

Page 24: ...e value NOTE When the temperature outside is measured at or below 0 F the dust sensor alarm will be disabled to allow economizer operation This is done because the compressor is disabled below 0 F and...

Page 25: ...NTER key to enter USER password 2000 3 Press UP or DOWN keys to scroll to System Config press ENTER key 4 Press UP or DOWN keys to scroll to Alarm Setup A4 press ENTER key 5 Press ENTER key to scroll...

Page 26: ...s UP or DOWN keys to scroll to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Supply Air Sensor C6 press ENTER key 5 Reference the Value to see the input of the sensor see Figure 37 6...

Page 27: ...Enthalpy where the outdoor temperature humidity and calculated dew point are considered for economizer operation on a cooling call To change the economizer type 1 Press MENU key to go to the Main Men...

Page 28: ...times to return to Main Menu screen See Table 9 for default settings for economizer operation FIGURE 40 Economizer Setup Enthalpy Control FIGURE 41 Economizer Setup TempHum Control TABLE 9 Economizer...

Page 29: ...economizer may be disabled by the LV if the system determines it needs to enter dehumidification mode More information about the dehumidification sequence can be found on page 12 and in LV1000 Service...

Page 30: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to insure optimal system performance Refer to instructions for the cylinder that is being utilize...

Page 31: ...plate charge weight NOTE Pressure table based on high speed condenser fan operation If condensing pressures appear elevated check condenser fan wiring See Condenser Fan Operation Full Load Cooling Ai...

Page 32: ...oss the appropriate terminals on the BG1000 terminal block to temporarily remove the unit from the security system Be sure to remove the jumper from the terminals after service has been completed See...

Reviews: