background image

Manual 2100-670 

Page 

29 of 32

Bard Guard Anti-Theft System Option

The unit has the option to be shipped from the factory 
with a low pressure switch, panel sensors and a 
speaker. These devices are used with the Bard Guard 
BG1000 anti-theft controller to provide an anti-theft 
measure. These sensors and switch form a loop that 
when connected to the BG1000 controller will cause 
the system to go into alarm if any of the front panels or 
coil assemblies are removed without being disarmed. 
The speaker provides an audible alert that the system 
is being tampered with. The Bard Guard anti-theft 
control sensor connection is wired to terminals 7 and 
8 on the wall unit. The speaker connection is wired to 
terminals 5 and 6 on the wall unit. See the BG1000 
Installation Instructions 2100-672 for directions on 
connecting the wall units to the BG1000 controller.

Smoke Detector Option

The unit is equipped with an input that requires a dry 
contact. This will disable unit operation and is intended 
to be used with a smoke detector (not supplied). When 
this input indicates a smoke event, the system will be 
shut down. The alarm will automatically clear when the 
alarm condition is no longer present. 

Inverter Option

The inverter is only used in applications where a 
generator is not present and the units must run during 
a power loss. The inverter will detect when power is lost 
to the wall unit and automatically turn on. The inverter 
will convert 48 vdc to 230 vac. It will also energize 
a power loss relay that will only allow the blower and 
economizer to run while powering the controller. A relay 
output from the inverter will also communicate to the 
controller that a power loss event has occurred. This 
data point will be communicated back to the LV1000 
(powered by -48 vdc all the time). This variable 
will then be available as a relay output for remote 
communication applications or communicated through 
the board Ethernet port for integration into building 
management system. The units will continue to run 
in economizer-only operation until power has been 
restored or the battery power has been depleted. 

The economizer may be disabled by the LV if the 
system determines it needs to enter dehumidification 
mode. More information about the dehumidification 
sequence can be found on page 12 and in LV1000 
Service Instructions 2100-673. In addition to dehum 
mode, the economizer may be disabled for 30 minutes 
(adjustable) if the dust sensor indicates the outdoor air 
is not acceptable for cooling. After the time has expired 
and on a call for cooling, the economizer will open 
again to sample the air. The unit will either return to 
normal operation or remain locked out for another 30 
minutes.

Emergency Ventilation Mode

If the shelter temperature is above the high 
temperature alarm 2 on the LV, the unit will be 
commanded into emergency ventilation mode. In this 
mode, the unit will open the economizer to 100%. The 
compressor may run during this mode. This will stay 
active until the LV returns the unit to normal operation. 
This mode is only available when connected to the LV. 

Model/Serial Number Configuration

The system will automatically configure some settings 
based on the model number input into the unit. The 
model and serial number are entered at the factory. 
During a program update, the model and serial number 
may be lost and need to be re-entered.
The unit will look at model number character number 
10 to determine if the economizer should be disabled. 
If the character is a E or e, the economizer operation 
will be disabled.
The unit will look at model number characters 8 and 9 
to determine how many heat stages are available. If the 
characters are 0Z, 0z, MZ, Mz, mZ or mz, the unit will 
be set to 0 stages of heat. If the characters are 05, m5 
or M5, the unit will be set to 1 stage of heat.

Electric Heat Option

Electric Heat Components

Electric Heating Element

The unit is optionally equipped with a 5kw heat strip. 
The heat strip is located next to the blower assembly 
and uses resistive heat. 

Thermal Overload

The heater assembly has a thermal overload wired in 
series with the heating element. This device has a 
cycling limit which opens at 130°F and resets at 80°F. 
The limit is also equipped with a redundant thermal 
fuse that will open at 150°F.

Electric Heat Operation

The heat strip will be activated on a call for heat. 
This call can be generated by the LV or the wall unit 
operating in stand alone mode.

Summary of Contents for FUSION-TEC HR58APB

Page 1: ...bardhvac com Manual 2100 670 Supersedes NEW Date 6 2 17 NOTE LV1000 Controller is required for operation when multiple HR58AP units are used SERVICE INSTRUCTIONS FUSION TEC WALL MOUNT AIR CONDITIONER...

Page 2: ...flow Alarms 18 Supply Air Temperature Alarm 18 Condenser Fan 18 Condenser Fan Components 18 Condenser Fan 18 High Pressure Transducer 19 High Pressure Transducer Alarm 19 Discharge Temperature Sensor...

Page 3: ...itch Filter Indicator Light 16 Figure 20 Verifying Freeze Switch Status 17 Figure 21 Adjusting Freezestat Alarm Delay 18 Figure 22 Verifying Condenser Fan Output 18 Figure 23 Fan Blade Setting 18 Figu...

Page 4: ...on is made See Additional Publications for information on codes and standards Sizing of systems for proposed installation should be based on heat loss and heat gain calculations made according to meth...

Page 5: ...s to be limited to the most extreme situations DANGER signs should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved WARNING Indicate s a...

Page 6: ...n case of power failure The controller is designed to manage temperature levels to a user defined setpoint via control output signals to the wall mount air conditioning system The TEC EYE connects to...

Page 7: ...u is accessible from the Status screen Setpoints Information and Data Alarm Log are available through the Quick Menu Pressing the UP or DOWN keys while on the Status screen will change the Quick Menu...

Page 8: ...and program version information Data Alarm Log The alarm log screens show a log of each alarm There will be a log for when alarm occurred and if the alarm auto clears it will show when the alarm clea...

Page 9: ...n each wall mount unit In stand alone mode the wall unit uses a continuous blower setting to circulate room air into the return air inlet and uses the return air temperature sensor to control room tem...

Page 10: ...trol will compare the space temperature to the space setpoint Based on how far away from the setpoint the temperature is the loop will output a cooling or heating capacity number between 0 and 100 The...

Page 11: ...zer operation so there are a total of 2 cooling stages see Figure 9 Heating The unit is equipped with 1 stage of electric heat see Figure 10 Staging The unit will stage the cooling components based on...

Page 12: ...l to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Suction Pr Sensor C11 press ENTER key 5 Verify the measurement displayed on screen is accurate see Figure 11 6 If the measurement n...

Page 13: ...the valve NOTE The unit must be off to perform this override 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN...

Page 14: ...the condition is no longer present This alarm cannot be adjusted Indoor Airflow Indoor Airflow Components Blower The unit is equipped with a blower that is driven by an electronically commutated moto...

Page 15: ...or DOWN keys to change to the desired value 7 Press ENTER key to save the value FIGURE 17 Dirty Filter Switch and Blower Status Switch FIGURE 16 Adjusting Air Flow Alarm Delay Differential Airflow Sw...

Page 16: ...tubing routed to the blower and vent areas of the unit The switch circuit consists of a normally open filter pressure switch The switch will open when the pressure differential goes above the setting...

Page 17: ...he evaporator coil To prevent the coil from freezing and potentially allowing liquid refrigerant from the evaporator to enter the compressor the switch will open when the temperature at this sensor is...

Page 18: ...ween 100 1200 rpm To view the output of the condenser fan 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys...

Page 19: ...arm When the high pressure transducer sensor value is out of range 0 650 PSIG the controller will generate a sensor failure alarm to indicate the sensor is not working properly This alarm is fixed and...

Page 20: ...ed moving as little air as possible If the discharge pressure continues to go down to 250 PSI the condenser fan will turn off The fan will remain off with the compressor running until the pressure rea...

Page 21: ...operation The monitoring device protects the unit against compressor contactor chatter and reverse compressor rotation during these situations Compressor protection device has an adjustable 30 second...

Page 22: ...can be changed by 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys to scroll to Adv System Config press EN...

Page 23: ...new override value and the damper will travel to that position NOTE This override will last for 5 minutes or until the Override is changed back to Disabled Dust Sensor The unit has a dust sensor insta...

Page 24: ...e value NOTE When the temperature outside is measured at or below 0 F the dust sensor alarm will be disabled to allow economizer operation This is done because the compressor is disabled below 0 F and...

Page 25: ...NTER key to enter USER password 2000 3 Press UP or DOWN keys to scroll to System Config press ENTER key 4 Press UP or DOWN keys to scroll to Alarm Setup A4 press ENTER key 5 Press ENTER key to scroll...

Page 26: ...s UP or DOWN keys to scroll to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Supply Air Sensor C6 press ENTER key 5 Reference the Value to see the input of the sensor see Figure 37 6...

Page 27: ...Enthalpy where the outdoor temperature humidity and calculated dew point are considered for economizer operation on a cooling call To change the economizer type 1 Press MENU key to go to the Main Men...

Page 28: ...times to return to Main Menu screen See Table 9 for default settings for economizer operation FIGURE 40 Economizer Setup Enthalpy Control FIGURE 41 Economizer Setup TempHum Control TABLE 9 Economizer...

Page 29: ...economizer may be disabled by the LV if the system determines it needs to enter dehumidification mode More information about the dehumidification sequence can be found on page 12 and in LV1000 Service...

Page 30: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to insure optimal system performance Refer to instructions for the cylinder that is being utilize...

Page 31: ...plate charge weight NOTE Pressure table based on high speed condenser fan operation If condensing pressures appear elevated check condenser fan wiring See Condenser Fan Operation Full Load Cooling Ai...

Page 32: ...oss the appropriate terminals on the BG1000 terminal block to temporarily remove the unit from the security system Be sure to remove the jumper from the terminals after service has been completed See...

Reviews: