background image

Manual 2100-670 

Page 

22 of 32

Upon receiving the alarm, the wall unit will remove 
the “Y” call from the CCM, resetting the status of the 
CCM. The alarm will stay present on the wall unit until 
manually cleared.
In addition to the CCM, the discharge pressure 
transducer is used to prevent a high pressure event. 
When the discharge pressure is above the discharge 
pressure alarm setpoint (set 30 pounds below high 
pressure switch, which is 650), the system will disable 
stage 2 of mechanical cooling.

Phase Monitor

Used only on  three phase equipment, the phase 
monitor is a compressor protection device that will 
prohibit operation of the compressor if the device senses 
a possible reverse-rotation situation due to incorrect 
phasing. On a call for compressor (and only compressor), 
the device will check incoming phase, check for severe 
voltage imbalance and check for proper frequency. 
Under nominal conditions, a green LED light will show 
on the face of the monitor. If there is improper phasing, 
voltage imbalance or frequency deviation, the device will 
show a red LED light and prohibit compressor operation.
If a fault condition occurs, reverse two of the supply 
leads to the unit. 

Do not reverse any of the unit factory 

wires as damage may occur.

Compressor Operation

The compressor will be enabled when the unit (in stand 
alone mode) or LV provide a cooling stage 1 call. The 
compressor call from the controller has several delays 
that may affect the start or stop time of the compressor 
in regards to the cooling demand. The compressor has 
a minimum on time of 180 seconds to prevent short 
cycling the compressor. The compressor also has a 
minimum off time of 120 seconds to prevent start 
ups before the pressure in the refrigeration system 
equalizes. When the second stage is engaged, it also 
has a minimum run time of 120 seconds to allow the 
system to stabilize before returning to single stage or 
shutting down.
These delays can be changed by:
1.  Press MENU key to go to the Main Menu screen.
2.  Press UP or DOWN keys and ENTER key to enter 

TECHNICIAN password 1313.

3.  Press UP or DOWN keys to scroll to 

Adv System 

Config

; press ENTER key.

4.  Press UP or DOWN keys to scroll to 

 Unit Config 

(B2)

; press ENTER key.

5.  Press ENTER key to scroll to 

Min On

,

 Min Off

,

 

Min On Same

,

 Unloader Del or Address Delay

 (see 

Figure 28).

6.  Press UP or DOWN keys to change the value.

7.  Press ENTER key to save value and move the 

cursor to next parameter or top of screen.

8.  Press ESCAPE key several times to return to Main 

Menu screen.

The address-based delay only applies to the wall unit 
when in stand alone mode. The controller will delay the 
unit compressor based on the value entered on screen 
B2 multiplied by the unit address. This is intended to 
keep multiple units from starting their compressors 
at the same time when there is a quick change in the 
load. When connected to the LV, this is taken care of by 
LV logic.

FIGURE 28

Adjusting Compressor Delays

Additional Compressor Alarms

Refrigerant Low Pressure Alarm

When the low pressure transducer indicates a pressure 
value less than the low pressure alarm setpoint of 
40 PSIG and there is an active call for cooling, 
the controller will disable the compressor (after a 
180-second delay). 

NOTE:

 The second call will be 

delayed based on the delay off value mentioned in the 

compressor section.

 The controller will try to run the 

refrigeration system two (2) times within 900 seconds 
before the alarm will lock the compressor out. This 
alarm needs to be manually cleared before compressor 
operation will resume.
To adjust the low pressure alarm settings:
1.  Press MENU key to go to the Main Menu screen.
2.  Press UP or DOWN keys and ENTER key to enter 

USER password 2000.

3.  Press UP or DOWN keys to scroll to 

System Config

press ENTER key.

4.  Press UP or DOWN keys to scroll to 

Alarm Setup 

(A6)

; press ENTER key.

5.  Press ENTER key to scroll to 

Delay

 to adjust how 

long the compressor waits before turning the 
compressor off (see Figure 29).

6.  Press UP or DOWN keys to adjust the time delay.
7.  Press ENTER key to scroll to 

Two Count Del

.

Summary of Contents for FUSION-TEC HR58APB

Page 1: ...bardhvac com Manual 2100 670 Supersedes NEW Date 6 2 17 NOTE LV1000 Controller is required for operation when multiple HR58AP units are used SERVICE INSTRUCTIONS FUSION TEC WALL MOUNT AIR CONDITIONER...

Page 2: ...flow Alarms 18 Supply Air Temperature Alarm 18 Condenser Fan 18 Condenser Fan Components 18 Condenser Fan 18 High Pressure Transducer 19 High Pressure Transducer Alarm 19 Discharge Temperature Sensor...

Page 3: ...itch Filter Indicator Light 16 Figure 20 Verifying Freeze Switch Status 17 Figure 21 Adjusting Freezestat Alarm Delay 18 Figure 22 Verifying Condenser Fan Output 18 Figure 23 Fan Blade Setting 18 Figu...

Page 4: ...on is made See Additional Publications for information on codes and standards Sizing of systems for proposed installation should be based on heat loss and heat gain calculations made according to meth...

Page 5: ...s to be limited to the most extreme situations DANGER signs should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved WARNING Indicate s a...

Page 6: ...n case of power failure The controller is designed to manage temperature levels to a user defined setpoint via control output signals to the wall mount air conditioning system The TEC EYE connects to...

Page 7: ...u is accessible from the Status screen Setpoints Information and Data Alarm Log are available through the Quick Menu Pressing the UP or DOWN keys while on the Status screen will change the Quick Menu...

Page 8: ...and program version information Data Alarm Log The alarm log screens show a log of each alarm There will be a log for when alarm occurred and if the alarm auto clears it will show when the alarm clea...

Page 9: ...n each wall mount unit In stand alone mode the wall unit uses a continuous blower setting to circulate room air into the return air inlet and uses the return air temperature sensor to control room tem...

Page 10: ...trol will compare the space temperature to the space setpoint Based on how far away from the setpoint the temperature is the loop will output a cooling or heating capacity number between 0 and 100 The...

Page 11: ...zer operation so there are a total of 2 cooling stages see Figure 9 Heating The unit is equipped with 1 stage of electric heat see Figure 10 Staging The unit will stage the cooling components based on...

Page 12: ...l to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Suction Pr Sensor C11 press ENTER key 5 Verify the measurement displayed on screen is accurate see Figure 11 6 If the measurement n...

Page 13: ...the valve NOTE The unit must be off to perform this override 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN...

Page 14: ...the condition is no longer present This alarm cannot be adjusted Indoor Airflow Indoor Airflow Components Blower The unit is equipped with a blower that is driven by an electronically commutated moto...

Page 15: ...or DOWN keys to change to the desired value 7 Press ENTER key to save the value FIGURE 17 Dirty Filter Switch and Blower Status Switch FIGURE 16 Adjusting Air Flow Alarm Delay Differential Airflow Sw...

Page 16: ...tubing routed to the blower and vent areas of the unit The switch circuit consists of a normally open filter pressure switch The switch will open when the pressure differential goes above the setting...

Page 17: ...he evaporator coil To prevent the coil from freezing and potentially allowing liquid refrigerant from the evaporator to enter the compressor the switch will open when the temperature at this sensor is...

Page 18: ...ween 100 1200 rpm To view the output of the condenser fan 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys...

Page 19: ...arm When the high pressure transducer sensor value is out of range 0 650 PSIG the controller will generate a sensor failure alarm to indicate the sensor is not working properly This alarm is fixed and...

Page 20: ...ed moving as little air as possible If the discharge pressure continues to go down to 250 PSI the condenser fan will turn off The fan will remain off with the compressor running until the pressure rea...

Page 21: ...operation The monitoring device protects the unit against compressor contactor chatter and reverse compressor rotation during these situations Compressor protection device has an adjustable 30 second...

Page 22: ...can be changed by 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys to scroll to Adv System Config press EN...

Page 23: ...new override value and the damper will travel to that position NOTE This override will last for 5 minutes or until the Override is changed back to Disabled Dust Sensor The unit has a dust sensor insta...

Page 24: ...e value NOTE When the temperature outside is measured at or below 0 F the dust sensor alarm will be disabled to allow economizer operation This is done because the compressor is disabled below 0 F and...

Page 25: ...NTER key to enter USER password 2000 3 Press UP or DOWN keys to scroll to System Config press ENTER key 4 Press UP or DOWN keys to scroll to Alarm Setup A4 press ENTER key 5 Press ENTER key to scroll...

Page 26: ...s UP or DOWN keys to scroll to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Supply Air Sensor C6 press ENTER key 5 Reference the Value to see the input of the sensor see Figure 37 6...

Page 27: ...Enthalpy where the outdoor temperature humidity and calculated dew point are considered for economizer operation on a cooling call To change the economizer type 1 Press MENU key to go to the Main Men...

Page 28: ...times to return to Main Menu screen See Table 9 for default settings for economizer operation FIGURE 40 Economizer Setup Enthalpy Control FIGURE 41 Economizer Setup TempHum Control TABLE 9 Economizer...

Page 29: ...economizer may be disabled by the LV if the system determines it needs to enter dehumidification mode More information about the dehumidification sequence can be found on page 12 and in LV1000 Service...

Page 30: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to insure optimal system performance Refer to instructions for the cylinder that is being utilize...

Page 31: ...plate charge weight NOTE Pressure table based on high speed condenser fan operation If condensing pressures appear elevated check condenser fan wiring See Condenser Fan Operation Full Load Cooling Ai...

Page 32: ...oss the appropriate terminals on the BG1000 terminal block to temporarily remove the unit from the security system Be sure to remove the jumper from the terminals after service has been completed See...

Reviews: