background image

Manual 2100-670 

Page 

9 of 32

Unit On/Off

The wall unit can be turned on and off from the TEC-
EYE. Turning the unit off with the following instructions 
will disable heating and cooling operation but may not 
disable the blower. The blower may continue to run 
if the unit or the LV1000 have the continuous blower 
option enabled.

NOTE:

 Blower will run if the unit is in stand alone 

mode.

To turn the unit on or off: 
1.  Press MENU key to go to the Main Menu screen.
2.  Press UP or DOWN keys and ENTER key to enter 

USER password 2000.

3.  Press UP or DOWN keys to scroll to 

On/Off

; press 

ENTER key.

4.  Press UP or DOWN keys to change value from On 

to Off or from Off to On.

5.  Press ESCAPE key several times to return to Main 

Menu screen.

The wall unit may also be turned off by certain alarms 
such as the smoke alarm input on the wall unit board 
or the return air temperature sensor failure when not 
connected to the LV1000.

Alarm Adjustment

Acknowledging/Clearing Alarms

Alarm conditions activate a red LED indicator that 
backlights the ALARM function key. As an option, an 
alarm condition may also be enunciated by an audible 
alarm signal. An alarm is acknowledged by pressing the 
ALARM key. This calls up alarm display screen(s) that 
provide a text message detailing the alarm condition(s). 
After an alarm condition is corrected, the alarm can be 
cleared by pressing the ALARM key for 3 seconds.
To clear all alarms, navigate to the end of the alarm list 
to the screen shown in Figure 5.

OPERATION

FIGURE 5

Clearing All Alarms

Stand Alone Mode

With the AC breakers turned on, each FUSION-TEC 
wall-mount unit has the capability to run without the 
LV1000 controller attached—this feature is called 
stand alone or orphan mode. This keeps the shelter 
between 60°F and 79°F (factory default settings) by 
the use of the factory-installed return air sensor in 
each wall-mount unit. In stand-alone mode, the wall 
unit uses a continuous blower setting to circulate room 
air into the return air inlet and uses the return air 
temperature sensor to control room temperature.
The wall-mount unit can be turned on and off with 
the TEC-EYE hand-held diagnostic tool. When ON is 
chosen, the wall unit will heat or cool. The blower will 
continue to run when OFF is chosen. If the wall unit is 
turned OFF by the TEC-EYE while in stand alone mode 
and power is interrupted, when repowered the blower 
will not run until the wall unit is turned back ON by the 
TEC-EYE (see 

Unit On/Off

).

To change default setpoints, refer to 

Setpoints

 on page 

7. 
During installation, the ability to run in stand alone 
mode allows deactivation of one of the existing, older 
wall-mount units, while keeping the shelter cool 
with the other unit still operating. Once the first of 
the Bard FUSION-TEC wall-mount units is installed, 
orphan mode can be enabled early in the installation—
keeping the climate inside the shelter stable and 
the installers comfortable while the remainder of the 
older equipment is removed and the remaining Bard 
FUSION-TEC wall-mount units and LV1000 controller 
are installed. 
Additionally, should any or all of the FUSION-TEC 
wall-mount units lose communication with the LV1000 
controller (such as during maintenance), they will 
continue to serve the shelter’s needs until a repair can 
be made. 

Temperature/Humidity Control

Temperature/Humidity Control Components

Return Air Temperature Sensor

The unit is equipped with a return air temperature 
sensor to monitor the space temperature when the unit 
is in stand alone mode. The return air sensor is located 
in the upper part of the return opening in such a way 
that it is exposed to the entering airstream. An alarm 
signal will be sent to the LV controller if the return air 
temperature sensor is disconnected. The temperature is 
measured with a 10k ohm NTC thermistor.
This sensor can be verified and adjusted by:
1.  Press MENU key to go to the Main Menu screen.

Summary of Contents for FUSION-TEC HR58APB

Page 1: ...bardhvac com Manual 2100 670 Supersedes NEW Date 6 2 17 NOTE LV1000 Controller is required for operation when multiple HR58AP units are used SERVICE INSTRUCTIONS FUSION TEC WALL MOUNT AIR CONDITIONER...

Page 2: ...flow Alarms 18 Supply Air Temperature Alarm 18 Condenser Fan 18 Condenser Fan Components 18 Condenser Fan 18 High Pressure Transducer 19 High Pressure Transducer Alarm 19 Discharge Temperature Sensor...

Page 3: ...itch Filter Indicator Light 16 Figure 20 Verifying Freeze Switch Status 17 Figure 21 Adjusting Freezestat Alarm Delay 18 Figure 22 Verifying Condenser Fan Output 18 Figure 23 Fan Blade Setting 18 Figu...

Page 4: ...on is made See Additional Publications for information on codes and standards Sizing of systems for proposed installation should be based on heat loss and heat gain calculations made according to meth...

Page 5: ...s to be limited to the most extreme situations DANGER signs should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved WARNING Indicate s a...

Page 6: ...n case of power failure The controller is designed to manage temperature levels to a user defined setpoint via control output signals to the wall mount air conditioning system The TEC EYE connects to...

Page 7: ...u is accessible from the Status screen Setpoints Information and Data Alarm Log are available through the Quick Menu Pressing the UP or DOWN keys while on the Status screen will change the Quick Menu...

Page 8: ...and program version information Data Alarm Log The alarm log screens show a log of each alarm There will be a log for when alarm occurred and if the alarm auto clears it will show when the alarm clea...

Page 9: ...n each wall mount unit In stand alone mode the wall unit uses a continuous blower setting to circulate room air into the return air inlet and uses the return air temperature sensor to control room tem...

Page 10: ...trol will compare the space temperature to the space setpoint Based on how far away from the setpoint the temperature is the loop will output a cooling or heating capacity number between 0 and 100 The...

Page 11: ...zer operation so there are a total of 2 cooling stages see Figure 9 Heating The unit is equipped with 1 stage of electric heat see Figure 10 Staging The unit will stage the cooling components based on...

Page 12: ...l to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Suction Pr Sensor C11 press ENTER key 5 Verify the measurement displayed on screen is accurate see Figure 11 6 If the measurement n...

Page 13: ...the valve NOTE The unit must be off to perform this override 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN...

Page 14: ...the condition is no longer present This alarm cannot be adjusted Indoor Airflow Indoor Airflow Components Blower The unit is equipped with a blower that is driven by an electronically commutated moto...

Page 15: ...or DOWN keys to change to the desired value 7 Press ENTER key to save the value FIGURE 17 Dirty Filter Switch and Blower Status Switch FIGURE 16 Adjusting Air Flow Alarm Delay Differential Airflow Sw...

Page 16: ...tubing routed to the blower and vent areas of the unit The switch circuit consists of a normally open filter pressure switch The switch will open when the pressure differential goes above the setting...

Page 17: ...he evaporator coil To prevent the coil from freezing and potentially allowing liquid refrigerant from the evaporator to enter the compressor the switch will open when the temperature at this sensor is...

Page 18: ...ween 100 1200 rpm To view the output of the condenser fan 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys...

Page 19: ...arm When the high pressure transducer sensor value is out of range 0 650 PSIG the controller will generate a sensor failure alarm to indicate the sensor is not working properly This alarm is fixed and...

Page 20: ...ed moving as little air as possible If the discharge pressure continues to go down to 250 PSI the condenser fan will turn off The fan will remain off with the compressor running until the pressure rea...

Page 21: ...operation The monitoring device protects the unit against compressor contactor chatter and reverse compressor rotation during these situations Compressor protection device has an adjustable 30 second...

Page 22: ...can be changed by 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys to scroll to Adv System Config press EN...

Page 23: ...new override value and the damper will travel to that position NOTE This override will last for 5 minutes or until the Override is changed back to Disabled Dust Sensor The unit has a dust sensor insta...

Page 24: ...e value NOTE When the temperature outside is measured at or below 0 F the dust sensor alarm will be disabled to allow economizer operation This is done because the compressor is disabled below 0 F and...

Page 25: ...NTER key to enter USER password 2000 3 Press UP or DOWN keys to scroll to System Config press ENTER key 4 Press UP or DOWN keys to scroll to Alarm Setup A4 press ENTER key 5 Press ENTER key to scroll...

Page 26: ...s UP or DOWN keys to scroll to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Supply Air Sensor C6 press ENTER key 5 Reference the Value to see the input of the sensor see Figure 37 6...

Page 27: ...Enthalpy where the outdoor temperature humidity and calculated dew point are considered for economizer operation on a cooling call To change the economizer type 1 Press MENU key to go to the Main Men...

Page 28: ...times to return to Main Menu screen See Table 9 for default settings for economizer operation FIGURE 40 Economizer Setup Enthalpy Control FIGURE 41 Economizer Setup TempHum Control TABLE 9 Economizer...

Page 29: ...economizer may be disabled by the LV if the system determines it needs to enter dehumidification mode More information about the dehumidification sequence can be found on page 12 and in LV1000 Service...

Page 30: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to insure optimal system performance Refer to instructions for the cylinder that is being utilize...

Page 31: ...plate charge weight NOTE Pressure table based on high speed condenser fan operation If condensing pressures appear elevated check condenser fan wiring See Condenser Fan Operation Full Load Cooling Ai...

Page 32: ...oss the appropriate terminals on the BG1000 terminal block to temporarily remove the unit from the security system Be sure to remove the jumper from the terminals after service has been completed See...

Reviews: