background image

Manual 2100-670 

Page 

32 of 32

MAINTENANCE

Standard Maintenance Procedures

4.  Manually spin fan and blower motors to ensure 

they turn freely. All motors are permanently 
lubricated, so no oil is necessary.

5.  Inspect free cooling damper actuator and linkage.
6.  Install new air filter; check for additional filter 

grilles internal to the structure.

7.  Inspect the control panel of the system.
 

•  Look for insect or rodent activity and remove 

any nesting materials.

 

•  Manually push contactor closed, observe for 

movement—contactor points should have 
minimal discoloration, no spalling or other 
signs of arcing. Replace if doubtful.

 

•  Check field and factory wiring for tightness and 

look for signs of overheating (discoloration of 
terminals or wire insulation).

8.  Ensure that supply and return registers are not 

obstructed, and more importantly, are not recycling 
the air to one another. Adjust supply louvers if 
necessary to direct discharge air away from any 
direct route to the return grille.

9.  Re-assemble wall-mount unit, turn breakers back on.  
10. Enable system to LV1000 controller (see LV1000 

Service Instructions 2100-673).

11. Repeat steps for additional wall-mount units.

Bard Guard Anti-Theft System Option

For situations that require an individual unit to be 
disconnected from the Bard Guard security system for 
an extended period of service time (longer than the 
maximum 250 minutes disarm time), place a jumper 
across the appropriate terminals on the BG1000 
terminal block to temporarily remove the unit from the 
security system. 

Be sure to remove the jumper from the 

terminals after service has been completed.

See the BG1000 Installation Instructions 2100-672 
for information on operating the BG1000 controller.

1.  Disable system from LV1000 controller (see 

LV1000 Service Instructions 2100-673).

2.  Turn off AC breakers at wall-mount units.
3.  Check inlet sides of condenser and evaporator coils 

for obstructions/debris—clean if necessary using a 
quality manufactured coil cleaning product specific 
for the evaporator or condenser coil.

 • Condenser coil: Remove the upper side panels 

from the condenser section. This will give 
clear access to the inlet side of the coil for 
cleaning. Follow the coil cleaner manufacturer’s 
directions for necessary safety gear and 
precautions, as well as for application and use. 
More than one application may be necessary. 
Rinse thoroughly.

 

•  Evaporator coil: Open filter access panels 

and remove filters. Apply specific evaporator 
cleaner directly to the inlet side of coil, being 
very careful not to overspray into insulation 
or surrounding panels and wiring. Residual 
cleaner and dissolved debris should drip into 
the drain pan and leave the unit through the 
condensate hose. More than one application 
may be necessary. Rinse thoroughly.

Cut hazard.

Wear gloves to avoid contact with sharp 

edges.

Failure to do so could result in personal 

injury.

!

CAUTION

Electrical shock hazard.
Disconnect all power supplies before 

servicing.

Failure to do so could result in electric shock 

or death.

!

WARNING

Summary of Contents for FUSION-TEC HR58APB

Page 1: ...bardhvac com Manual 2100 670 Supersedes NEW Date 6 2 17 NOTE LV1000 Controller is required for operation when multiple HR58AP units are used SERVICE INSTRUCTIONS FUSION TEC WALL MOUNT AIR CONDITIONER...

Page 2: ...flow Alarms 18 Supply Air Temperature Alarm 18 Condenser Fan 18 Condenser Fan Components 18 Condenser Fan 18 High Pressure Transducer 19 High Pressure Transducer Alarm 19 Discharge Temperature Sensor...

Page 3: ...itch Filter Indicator Light 16 Figure 20 Verifying Freeze Switch Status 17 Figure 21 Adjusting Freezestat Alarm Delay 18 Figure 22 Verifying Condenser Fan Output 18 Figure 23 Fan Blade Setting 18 Figu...

Page 4: ...on is made See Additional Publications for information on codes and standards Sizing of systems for proposed installation should be based on heat loss and heat gain calculations made according to meth...

Page 5: ...s to be limited to the most extreme situations DANGER signs should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved WARNING Indicate s a...

Page 6: ...n case of power failure The controller is designed to manage temperature levels to a user defined setpoint via control output signals to the wall mount air conditioning system The TEC EYE connects to...

Page 7: ...u is accessible from the Status screen Setpoints Information and Data Alarm Log are available through the Quick Menu Pressing the UP or DOWN keys while on the Status screen will change the Quick Menu...

Page 8: ...and program version information Data Alarm Log The alarm log screens show a log of each alarm There will be a log for when alarm occurred and if the alarm auto clears it will show when the alarm clea...

Page 9: ...n each wall mount unit In stand alone mode the wall unit uses a continuous blower setting to circulate room air into the return air inlet and uses the return air temperature sensor to control room tem...

Page 10: ...trol will compare the space temperature to the space setpoint Based on how far away from the setpoint the temperature is the loop will output a cooling or heating capacity number between 0 and 100 The...

Page 11: ...zer operation so there are a total of 2 cooling stages see Figure 9 Heating The unit is equipped with 1 stage of electric heat see Figure 10 Staging The unit will stage the cooling components based on...

Page 12: ...l to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Suction Pr Sensor C11 press ENTER key 5 Verify the measurement displayed on screen is accurate see Figure 11 6 If the measurement n...

Page 13: ...the valve NOTE The unit must be off to perform this override 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN...

Page 14: ...the condition is no longer present This alarm cannot be adjusted Indoor Airflow Indoor Airflow Components Blower The unit is equipped with a blower that is driven by an electronically commutated moto...

Page 15: ...or DOWN keys to change to the desired value 7 Press ENTER key to save the value FIGURE 17 Dirty Filter Switch and Blower Status Switch FIGURE 16 Adjusting Air Flow Alarm Delay Differential Airflow Sw...

Page 16: ...tubing routed to the blower and vent areas of the unit The switch circuit consists of a normally open filter pressure switch The switch will open when the pressure differential goes above the setting...

Page 17: ...he evaporator coil To prevent the coil from freezing and potentially allowing liquid refrigerant from the evaporator to enter the compressor the switch will open when the temperature at this sensor is...

Page 18: ...ween 100 1200 rpm To view the output of the condenser fan 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys...

Page 19: ...arm When the high pressure transducer sensor value is out of range 0 650 PSIG the controller will generate a sensor failure alarm to indicate the sensor is not working properly This alarm is fixed and...

Page 20: ...ed moving as little air as possible If the discharge pressure continues to go down to 250 PSI the condenser fan will turn off The fan will remain off with the compressor running until the pressure rea...

Page 21: ...operation The monitoring device protects the unit against compressor contactor chatter and reverse compressor rotation during these situations Compressor protection device has an adjustable 30 second...

Page 22: ...can be changed by 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys to scroll to Adv System Config press EN...

Page 23: ...new override value and the damper will travel to that position NOTE This override will last for 5 minutes or until the Override is changed back to Disabled Dust Sensor The unit has a dust sensor insta...

Page 24: ...e value NOTE When the temperature outside is measured at or below 0 F the dust sensor alarm will be disabled to allow economizer operation This is done because the compressor is disabled below 0 F and...

Page 25: ...NTER key to enter USER password 2000 3 Press UP or DOWN keys to scroll to System Config press ENTER key 4 Press UP or DOWN keys to scroll to Alarm Setup A4 press ENTER key 5 Press ENTER key to scroll...

Page 26: ...s UP or DOWN keys to scroll to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Supply Air Sensor C6 press ENTER key 5 Reference the Value to see the input of the sensor see Figure 37 6...

Page 27: ...Enthalpy where the outdoor temperature humidity and calculated dew point are considered for economizer operation on a cooling call To change the economizer type 1 Press MENU key to go to the Main Men...

Page 28: ...times to return to Main Menu screen See Table 9 for default settings for economizer operation FIGURE 40 Economizer Setup Enthalpy Control FIGURE 41 Economizer Setup TempHum Control TABLE 9 Economizer...

Page 29: ...economizer may be disabled by the LV if the system determines it needs to enter dehumidification mode More information about the dehumidification sequence can be found on page 12 and in LV1000 Service...

Page 30: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to insure optimal system performance Refer to instructions for the cylinder that is being utilize...

Page 31: ...plate charge weight NOTE Pressure table based on high speed condenser fan operation If condensing pressures appear elevated check condenser fan wiring See Condenser Fan Operation Full Load Cooling Ai...

Page 32: ...oss the appropriate terminals on the BG1000 terminal block to temporarily remove the unit from the security system Be sure to remove the jumper from the terminals after service has been completed See...

Reviews: