background image

Manual 2100-670 

Page 

4 of 32

GENERAL INFORMATION

Free Cooling Unit System

This Bard Free Cooling Unit System is composed of 
FUSION-TEC wall-mounted air conditioners matched 
with an LV1000 lead/lag controller. The wall mounts 
are specifically engineered for telecom/motor control 
center rooms. 

NOTE:

 

The LV1000 lead/lag controller and FUSION-

TEC wall-mount units are designed specifically 

to work together. The controller cannot run 

other Bard models or other brands of systems, 

nor can other controllers run the FUSION-TEC 

wall-mount units. They are a complete system, 

and must be used together. 

Wall-Mount Air Conditioner Units

The FUSION-TEC units operate on VAC power. The 
units will supply 100% of rated cooling airflow in free 
cooling mode with ability to exhaust the same amount 
through the unit itself without any additional relief 
openings in the shelter.
Each of these units are fully charged with refrigerant 
and have optional auxiliary heat.

General

The equipment covered in this manual is to be installed 
by trained, experienced service and installation 
technicians.
The refrigerant system is completely assembled and 
charged. All internal wiring is complete.
The unit is designed for use without duct work. Flanges 
are provided for transition from unit to wall grilles.
These instructions explain the recommended method 
to install the air cooled self-contained unit and the 
electrical wiring connections to the unit.
These instructions and any instructions packaged with 
any separate equipment required to make up the entire 
air conditioning system should be carefully read before 
beginning the installation. Note particularly any tags 
and/or labels attached to the equipment.
While these instructions are intended as a general 
recommended guide, they do not supersede any national 
and/or local codes in any way. Authorities having 
jurisdiction should be consulted before the installation is 
made. See 

Additional Publications

 for information 

on codes and standards.
Sizing of systems for proposed installation should be 
based on heat loss and heat gain calculations made 
according to methods of Air Conditioning Contractors of 
America (ACCA). The supply flange should be installed 
in accordance with the 

Standards of the National 

Fire Protection Association for the Installation of Air 

Conditioning and Ventilating Systems of Other Than 

Residence Type, NFPA No. 90A

, and 

Residence Type 

Warm Air Heating and Air Conditioning Systems, NFPA 

No. 90B

. Where local regulations are at a variance with 

instructions, installer should adhere to local codes.

Shipping Damage

Upon receipt of equipment, the cartons should be 
checked for external signs of shipping damage. If 
damage is found, the receiving party must contact 
the last carrier immediately, preferably in writing, 
requesting inspection by the carrier’s agent.
These units must remain in upright position at all 
times.

Additional Publications

These publications can help when installing  the 
furnace. They can usually be found at the local library 
or purchased directly from the publisher. Be sure to 
consult the current edition of each standard.

National Electrical Code ......................ANSI/NFPA 70
Standard for the Installation of Air Conditioning  
and Ventilating Systems  ...................ANSI/NFPA 90A
Standard for Warm Air Heating  
and Air Conditioning Systems ............ANSI/NFPA 90B
Load Calculation for Residential Winter  
and Summer Air Conditioning ............. ACCA Manual J

For more information, contact these publishers:

Air Conditioning Contractors of America (ACCA)

 

1712 New Hampshire Ave. N.W. 
Washington, DC 20009 
Telephone: (202) 483-9370  Fax: (202) 234-4721

American National Standards Institute (ANSI

11 West Street, 13th Floor 
New York, NY 10036 
Telephone: (212) 642-4900  Fax: (212) 302-1286

American Society of Heating, Refrigeration and Air 

Conditioning Engineers, Inc. (ASHRAE)

 

1791 Tullie Circle, N.E. 
Atlanta, GA 30329-2305 
Telephone: (404) 636-8400  Fax: (404) 321-5478

National Fire Protection Association (NFPA

Batterymarch Park 
P. O. Box 9101 
Quincy, MA 02269-9901 
Telephone: (800) 344-3555  Fax: (617) 984-7057

Summary of Contents for FUSION-TEC HR58APB

Page 1: ...bardhvac com Manual 2100 670 Supersedes NEW Date 6 2 17 NOTE LV1000 Controller is required for operation when multiple HR58AP units are used SERVICE INSTRUCTIONS FUSION TEC WALL MOUNT AIR CONDITIONER...

Page 2: ...flow Alarms 18 Supply Air Temperature Alarm 18 Condenser Fan 18 Condenser Fan Components 18 Condenser Fan 18 High Pressure Transducer 19 High Pressure Transducer Alarm 19 Discharge Temperature Sensor...

Page 3: ...itch Filter Indicator Light 16 Figure 20 Verifying Freeze Switch Status 17 Figure 21 Adjusting Freezestat Alarm Delay 18 Figure 22 Verifying Condenser Fan Output 18 Figure 23 Fan Blade Setting 18 Figu...

Page 4: ...on is made See Additional Publications for information on codes and standards Sizing of systems for proposed installation should be based on heat loss and heat gain calculations made according to meth...

Page 5: ...s to be limited to the most extreme situations DANGER signs should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved WARNING Indicate s a...

Page 6: ...n case of power failure The controller is designed to manage temperature levels to a user defined setpoint via control output signals to the wall mount air conditioning system The TEC EYE connects to...

Page 7: ...u is accessible from the Status screen Setpoints Information and Data Alarm Log are available through the Quick Menu Pressing the UP or DOWN keys while on the Status screen will change the Quick Menu...

Page 8: ...and program version information Data Alarm Log The alarm log screens show a log of each alarm There will be a log for when alarm occurred and if the alarm auto clears it will show when the alarm clea...

Page 9: ...n each wall mount unit In stand alone mode the wall unit uses a continuous blower setting to circulate room air into the return air inlet and uses the return air temperature sensor to control room tem...

Page 10: ...trol will compare the space temperature to the space setpoint Based on how far away from the setpoint the temperature is the loop will output a cooling or heating capacity number between 0 and 100 The...

Page 11: ...zer operation so there are a total of 2 cooling stages see Figure 9 Heating The unit is equipped with 1 stage of electric heat see Figure 10 Staging The unit will stage the cooling components based on...

Page 12: ...l to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Suction Pr Sensor C11 press ENTER key 5 Verify the measurement displayed on screen is accurate see Figure 11 6 If the measurement n...

Page 13: ...the valve NOTE The unit must be off to perform this override 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN...

Page 14: ...the condition is no longer present This alarm cannot be adjusted Indoor Airflow Indoor Airflow Components Blower The unit is equipped with a blower that is driven by an electronically commutated moto...

Page 15: ...or DOWN keys to change to the desired value 7 Press ENTER key to save the value FIGURE 17 Dirty Filter Switch and Blower Status Switch FIGURE 16 Adjusting Air Flow Alarm Delay Differential Airflow Sw...

Page 16: ...tubing routed to the blower and vent areas of the unit The switch circuit consists of a normally open filter pressure switch The switch will open when the pressure differential goes above the setting...

Page 17: ...he evaporator coil To prevent the coil from freezing and potentially allowing liquid refrigerant from the evaporator to enter the compressor the switch will open when the temperature at this sensor is...

Page 18: ...ween 100 1200 rpm To view the output of the condenser fan 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys...

Page 19: ...arm When the high pressure transducer sensor value is out of range 0 650 PSIG the controller will generate a sensor failure alarm to indicate the sensor is not working properly This alarm is fixed and...

Page 20: ...ed moving as little air as possible If the discharge pressure continues to go down to 250 PSI the condenser fan will turn off The fan will remain off with the compressor running until the pressure rea...

Page 21: ...operation The monitoring device protects the unit against compressor contactor chatter and reverse compressor rotation during these situations Compressor protection device has an adjustable 30 second...

Page 22: ...can be changed by 1 Press MENU key to go to the Main Menu screen 2 Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313 3 Press UP or DOWN keys to scroll to Adv System Config press EN...

Page 23: ...new override value and the damper will travel to that position NOTE This override will last for 5 minutes or until the Override is changed back to Disabled Dust Sensor The unit has a dust sensor insta...

Page 24: ...e value NOTE When the temperature outside is measured at or below 0 F the dust sensor alarm will be disabled to allow economizer operation This is done because the compressor is disabled below 0 F and...

Page 25: ...NTER key to enter USER password 2000 3 Press UP or DOWN keys to scroll to System Config press ENTER key 4 Press UP or DOWN keys to scroll to Alarm Setup A4 press ENTER key 5 Press ENTER key to scroll...

Page 26: ...s UP or DOWN keys to scroll to I O Config press ENTER key 4 Press UP or DOWN keys to scroll to Supply Air Sensor C6 press ENTER key 5 Reference the Value to see the input of the sensor see Figure 37 6...

Page 27: ...Enthalpy where the outdoor temperature humidity and calculated dew point are considered for economizer operation on a cooling call To change the economizer type 1 Press MENU key to go to the Main Men...

Page 28: ...times to return to Main Menu screen See Table 9 for default settings for economizer operation FIGURE 40 Economizer Setup Enthalpy Control FIGURE 41 Economizer Setup TempHum Control TABLE 9 Economizer...

Page 29: ...economizer may be disabled by the LV if the system determines it needs to enter dehumidification mode More information about the dehumidification sequence can be found on page 12 and in LV1000 Service...

Page 30: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to insure optimal system performance Refer to instructions for the cylinder that is being utilize...

Page 31: ...plate charge weight NOTE Pressure table based on high speed condenser fan operation If condensing pressures appear elevated check condenser fan wiring See Condenser Fan Operation Full Load Cooling Ai...

Page 32: ...oss the appropriate terminals on the BG1000 terminal block to temporarily remove the unit from the security system Be sure to remove the jumper from the terminals after service has been completed See...

Reviews: