Manual 2100-620A
Page
97 of 107
Screen
Menu Item
Value
Description
HVAC 2 Fail Relay 7
Off
"On" to allow artificial manipulation of
HVAC 2 fail relay action
Manual Position
On/Off
Change to "Off" to artificially force
HVAC 2 fail relay action
Relay 7 Status
On
Current Status of HVAC 2 Fail Relay
(On means no Relay action)
Lag Unit Run Relay 8
Off
"On" to allow artificial manipulation of
Lag Unit Run Alarm Relay action
Manual Position
On/Off
Change to "Off" to artifificially force Lag
Unit Run Relay action
Relay 8 Status
On
Current Status of Lag Unit Run Alarm
Relay (On means no Relay Action)
Factory
Configuration
Temperature Units
°F
°C units available as well
Pressure Units
PSI
N/A
Force Clock Enable
Yes
Clock Mode
24 hour
12 hour available
Disable Buzzer
Yes
Audible buzzer available
Startup Delay
1 second
Enable Unit
On/Off
By digit input
off
N/A
By supervisor
off
N/A
By pLAN network
off
N/A
By schedule
off
N/A
Unit Control
Custom 1
off
N/A
Custom 2
off
N/A
Custom 3
off
N/A
Custom 4
off
N/A
Analog Input Fitering
Enable
No
N/A
Input 1
19 seconds
N/A
Input 2
19 seconds
N/A
Input 3
19 seconds
N/A
Input 4
19 seconds
N/A
Input 5
19 seconds
N/A
Factory Settings
Manual Cont. Reset Enable
Yes
Time
5 minutes
Local Setpoint Reset
60 minutes
Allows only 60 minutes for setpoint
changes
PW/Return Delay
300 seconds
Display goes to status page and
backlight shuts off in 5 minutes
Summary of Contents for D36A2P/BLD.10304
Page 6: ...Manual 2100 620A Page 6 of 107 ...
Page 7: ...Manual 2100 620A Page 7 of 107 SECTION 1 INSTALLATION INSTRUCTIONS ...
Page 39: ...Manual 2100 620A Page 39 of 107 SECTION 2 SERVICE INSTRUCTIONS ...
Page 73: ...Manual 2100 620A Page 73 of 107 SECTION 3 PARTS MANUAL ...
Page 90: ...Manual 2100 620A Page 90 of 107 ...
Page 91: ...Manual 2100 620A Page 91 of 107 SECTION 4 APPENDICES ...