Manual 2100-620A
Page
30 of 107
RS485
R+T+ / R-T-
FIGURE 1.23
Communication Wiring: Termination at the First Wall-Mount Unit
RS485
R+T+ / R-T-
1. From the controller, extend the shielded cable through a separate conduit
and route to the provided terminal block next to the wall-mount control
board.
Note that the terminal block label is clearly marked “+” and “-”. These
connections are polarity-sensitive. Two-wire communication from control
board is prewired to terminal block. Make sure to match "+" and "-"
symbols on controller terminal blocks.
2. Connect the wires matching the terminal
designations (+/-) of the controller terminals.
Leave the drain wire loose.
3. Connect another cable in a similar
fashion (“daisy chain”) to route in
conduit to the second wall-mount unit.
Connect both drain wires with wire nut.
Wall-Mount Unit 1
Control Board
Wall-Mount Unit 1
Control Board
From LC1000-100
or LC1500-100
Controller
RS485
R+T+ / R-T-
Wall-Mount Unit 1
Control Board
From LC1000-100
or LC1500-100
Controller
From LC1000-100
or LC1500-100
Controller
To Wall-Mount Unit 2
Control Board RS485
Summary of Contents for D36A2P/BLD.10304
Page 6: ...Manual 2100 620A Page 6 of 107 ...
Page 7: ...Manual 2100 620A Page 7 of 107 SECTION 1 INSTALLATION INSTRUCTIONS ...
Page 39: ...Manual 2100 620A Page 39 of 107 SECTION 2 SERVICE INSTRUCTIONS ...
Page 73: ...Manual 2100 620A Page 73 of 107 SECTION 3 PARTS MANUAL ...
Page 90: ...Manual 2100 620A Page 90 of 107 ...
Page 91: ...Manual 2100 620A Page 91 of 107 SECTION 4 APPENDICES ...