Manual 2100-620A
Page
95 of 107
Screen
Menu Item
Value
Description
Digital Inputs
Smoke Detector DI 1 Status
Open
Hyd. Detector DI 2 Status
Open
Generator Run DI 3 Status
Open
Relay Outputs
Smoke Alarm Relay 1 Status
On
High Temp 2 Relay 4 Status
On
Low Temp Relay 5 Status
On
HVAC 1 Fail Relay 6 Status
On
HVAC 2 Fail Relay 7 Status
On
Lag Unit Run Relay 8 Status
On
Alarm History
Use the Up/Down arrows to scroll
through the latest alarms/conditions
Technician
Information
Bard Code
Inside controller
"Unit Controller" would be a pre-
programmed wall-mount unit board
Version
(Current version)
Bios
(Current bios)
Root
(Current root)
Flshram
N/A
Internal memory specifications
Power Cycle
N/A
Count of power initiations
BMS Configuration
BMS Port 1 Protocol
Carel
BMS Port 1 Address
1
BMS Baud Rate
19200
Service Settings
Probe Adjustment
Input B01 Offset
0
Calibrating indoor sensor if necessary
Input B01 Value
(Current Temp)
Current temperature plus offset
Control Settings
Remote Sensors
0
Enter the amount of extra remote
sensors
Control to
Average
Choose "Average" or "Highest"
U1 Run Test
No
"Yes" to begin Run Test Unit 1
U2 Run Test
No
"Yes" to begin Run Test Unit 2
Manual Management
Analog Inputs
Manual Control B001
Off
On to manually change temperature
seen by controller
Summary of Contents for D36A2P/BLD.10304
Page 6: ...Manual 2100 620A Page 6 of 107 ...
Page 7: ...Manual 2100 620A Page 7 of 107 SECTION 1 INSTALLATION INSTRUCTIONS ...
Page 39: ...Manual 2100 620A Page 39 of 107 SECTION 2 SERVICE INSTRUCTIONS ...
Page 73: ...Manual 2100 620A Page 73 of 107 SECTION 3 PARTS MANUAL ...
Page 90: ...Manual 2100 620A Page 90 of 107 ...
Page 91: ...Manual 2100 620A Page 91 of 107 SECTION 4 APPENDICES ...