GENERAL INFORMATION
DC FREE COOLING UNIT SYSTEM (DC-FCU)
The Bard DC Free Cooling Unit system is composed of two (2) D-Series DUAL-TEC™ wall-mounted air conditioners
matched with one (1) Bard-Link
TM
PLC lead/lag controller. The D-Series, specifically engineered for the telecom
market, can provide outdoor air cooling during power loss situations through the use of onsite -48VDC positive
ground battery banks.
NOTE:
The Bard-Link
TM
PLC lead/lag controller and the D-Series wall-mount units are designed specifically to
work together. The PLC controller cannot run other Bard models or other brands of systems, nor can other
controllers or thermostats run the D-Series wall-mount units. They are a complete system, and must be used
together.
WALL-MOUNT AIR CONDITIONER UNITS
The D-Series units operate on both VAC and VDC power under normal power supply conditions. If there is loss of VAC
power supply (shore and/or back-up generator) the unit will continue to operate as free cooling or ventilation system
using the shelter’s VDC power. The indoor blower and free cooling unit operate from -48VDC and no inverter is required.
The units will supply 100% of rated cooling airflow in free cooling mode with ability to exhaust the same amount
through the unit itself without any additional relief openings in the shelter.
Each of these units are fully charged with refrigerant and have auxilliary heat installed.
BARD-LINK
TM
PLC CONTROLLER
Two models: LC1000-100 and LC1500-100 (controllers and accessories included with controllers shown below).
Remote Temperature
Sensor with 35' Cable
Programmable
Logic Controller
with Attached
66 Punch-Down
Block
Communication
EMI Filters
Programmable Logic
Controller
TEC-EYE Hand-Held
Diagnostic Tool
LC1000-100 Series – New Shelters Only
LC1500-100 Series – EOL and All HVAC Replacement Projects
TEC-EYE Hand-Held
Diagnostic Tool
Communication
EMI Filters
VDC
Smoke
Detector
VDC
Hydrogen
Detector
OPTIONAL
8301-061
Remote Temperature
Sensor with 35' Cable
Summary of Contents for D36A2P/BLD.10304
Page 6: ...Manual 2100 620A Page 6 of 107 ...
Page 7: ...Manual 2100 620A Page 7 of 107 SECTION 1 INSTALLATION INSTRUCTIONS ...
Page 39: ...Manual 2100 620A Page 39 of 107 SECTION 2 SERVICE INSTRUCTIONS ...
Page 73: ...Manual 2100 620A Page 73 of 107 SECTION 3 PARTS MANUAL ...
Page 90: ...Manual 2100 620A Page 90 of 107 ...
Page 91: ...Manual 2100 620A Page 91 of 107 SECTION 4 APPENDICES ...