Heating U1/U2 Run
Minutes
Heating run time
Heating U1/U2 Start
#
Heating initiations
Main Menu
(MENU key to enter, use UP/DOWN arrow keys to scroll)
On/Off Unit
Unit Address
1
Physical address of controller
Power by Display On/Off
Status
On
"OFF by Keyboard" system has been
turned off at controller
Setpoints
All setpoint changes are
limited to 60 minutes
Cooling Setpoint
77°F
Heating Setpoint
60°F
Cooling Stg. Diff.
5°F
Heating Stg. Diff.
2°F
Stage Delay
10 seconds
FreeCool
55°F
FreeCool Enable
50°F
Differential
10°F
DC OA-Return Diff.
10°F
Supply Temp Low Limit
45°F
Differential
5°F
Alarm Delay
10 seconds
Run Test Time
60 seconds
Low Alarm
45°F
High Alarm
85°F
High Alarm 2
90°F
Blower Settings
Continuous
None
"Lead Only" or "Both" also available
Blower Speeds
Heat
7.0V
Control voltage supplied from wall-
mount unit control boards to blower in
heat
Econ
7.0V
Control voltage supplied from wall-
mount unit control boards to blower in
regular DC free cooling
Econ Low Temp
3.8V
Control voltage supplied from wall-
mount unit control boards to blower in
low ambient condition DC free cooling
Full Load
6.3V
Control voltage supplied from wall-
mount unit control boards to blower in
mechanical cooling
Summary of Contents for D36A2P/BLD.10304
Page 6: ...Manual 2100 620A Page 6 of 107 ...
Page 7: ...Manual 2100 620A Page 7 of 107 SECTION 1 INSTALLATION INSTRUCTIONS ...
Page 39: ...Manual 2100 620A Page 39 of 107 SECTION 2 SERVICE INSTRUCTIONS ...
Page 73: ...Manual 2100 620A Page 73 of 107 SECTION 3 PARTS MANUAL ...
Page 90: ...Manual 2100 620A Page 90 of 107 ...
Page 91: ...Manual 2100 620A Page 91 of 107 SECTION 4 APPENDICES ...