Manual 2100-620A
Page
68 of 107
FIGURE 2.23
Verifying Incoming Voltage: VDC
48VDC Shelter System
Voltage Range:
40VDC – 56VDC
Typical Running Range:
48VDC – 53VDC
Multimeter set to VDC
Shelter supply breaker in ON position Bard
system breaker in OFF position
52VDC
Displayed voltage must be within this range