1
Rear of the side glass pane
2
Flammable mantel piece
3
Insulation plate
Figure 18. Side mantel piece clearances
Width of mantel piece / Depth of mantel piece
A
5 cm
B
10 cm
C
15 cm
4.9
Clearances for concentric flue system
Do not insulate the concentric flue pipe.
Concentric flue pipe safety distances to flammable material:
• Vertical pipe (all sides): B = minimum 2.5 cm.
• Horizontal pipe top: A = minimum 7.5 cm.
• Horizontal pipe bottom and sides: B = minimum 2.5 cm.
The figures show the minimum clearances from a horizontal and a vertical concentric flue
pipe to flammable material.
Clearances
30
Gas Fire Panorama 70-55