Figure 14 shows the minimum thickness of the insulation plates and the minimum
clearances to a non-flammable ceiling
Make sure the total area of the convection air outlet opening is minimum 300 cm
2
.
1
Chimney enclosure
2
Convection air outlet opening
3
Non-Flammable ceiling
4
Insulation plate (false ceiling)
5
Insulation plates
Figure 14. Clearances to non-flammable ceiling - Front view
Table 7: Minimum dimension and clearance to non-flammable ceiling
With false ceiling, minimum
25 mm thickness
Without false ceiling
h
Area of the convection air
outlet opening
Minimum 300 cm
2
Minimum 20 cm open space
between ceiling and chim-
ney enclosure
H
Height of the false ceiling
Minimum 25 mm (= thick-
ness false ceiling)
Not applicable (the top side
of the chimney enclosure is
open with a clearance of
minimum 20 cm to the ceil-
ing.
A
Distance between convec-
tion air outlet opening and
ceiling
Minimum 13 cm
Minimum 20 cm open space
between ceiling and chim-
ney enclosure
Clearances
26
Gas Fire Panorama 70-55
Summary of Contents for 70-55 PF2
Page 1: ...Installation and maintenance manual Gas Fire Panorama 70 55 PF2 Serial number Production date...
Page 50: ...2 Remove the side panels and front panel Maintenance 50 Gas Fire Panorama 70 55...
Page 71: ...9 3 Gas Fire Panorama 70 55 PF2 with 4 cm frame Dimensions Gas Fire Panorama 70 55 71...
Page 73: ...9 5 Gas Fire Panorama 70 55 PF2 with 6 cm frame Dimensions Gas Fire Panorama 70 55 73...
Page 75: ...9 7 Gas Fire Panorama 70 55 PF2 with 10 cm frame Dimensions Gas Fire Panorama 70 55 75...
Page 78: ...9 10 Operating unit Dimensions 78 Gas Fire Panorama 70 55...
Page 81: ...11 EU Declaration of Conformity EU Declaration of Conformity Gas Fire Panorama 70 55 81...
Page 82: ...EU Declaration of Conformity 82 Gas Fire Panorama 70 55...
Page 83: ...EU Declaration of Conformity Gas Fire Panorama 70 55 83...