background image

Register

(4xxxx)

Output

#

Output Type

Units

I/O Range

Holding Register

Representation

Terminal

Block Labels

Min. Value Max.

Value

Min.

(Dec.)

Max.

(Dec.)

505

5

Switch Power 3

SP3

506

6

Switch Power 4

SP4

Modbus Addressing Convention

All Modbus addresses refer to Modbus holding registers. When writing your own Modbus scripts, use the appropriate

commands for interfacing to holding registers. (Because Modbus numbering begins at 1, users need to subtract 1 from the

register address given to form the numeric value entered into the “address” field of the Modbus RTU protocol command

string.) Parameter description headings refer to addresses in the range of 40000 as is customary with Modbus convention.

Modbus Register Configuration

Change the factory default settings for the inputs, outputs, and device operations using the device Modbus registers. To

change parameters, set the data radio network to Modbus mode and assign the data radio a valid Modbus slave ID.

Generic input or output parameters are grouped together based on the device input or output number: input 1, input 2,

output 1 etc. Operation type specific parameters (discrete, counter, analog 4 to 20 mA) are grouped together based on the

I/O type number: analog 1, analog 2, counter 1, etc. Not all inputs or outputs may be available for all models. To

determine which specific I/O is available on your model, refer to the Modbus Input/Output Register Maps listed in the

device's datasheet. For more information about registers, refer to the 

MultiHop Product Manual

 (p/n 151317).

Factory Default Configuration

Discrete Inputs (NPN)

Enable

Sample

Boost

Enable

Boost

Warmup

Boost

Voltage

Extended

Input

Read

NPN/PNP

Sample

High

Sample

Low

ON

40 ms

OFF

OFF

OFF

OFF

NPN

OFF

OFF

Analog Inputs

Enable

Sample

Boost

Enable

Boost

Warmup

Boost

Voltage

Extended

Input

Read

Analog

Max

Analog

Min

Enable

Fullscale

ON

1 sec

OFF

OFF

OFF

OFF

20000

0

ON

Thermistor Inputs

Enable

Sample

Boost

Enable

Boost

Warmup

Boost

Voltage

Extende

d Input

Read

Analog

Max

Analog

Min

Enable

Fullscal

e

Enable

Deg F

Temp

Scaling

ON

1 sec

OFF

OFF

OFF

OFF

32767

-32768

OFF

Deg F

× 20

Counter Inputs

Enable

Sample

Boost Enable

Boost Warmup

Boost Voltage

Extended Input

Read

Freq or Event

Counter

ON

1 sec

OFF

OFF

OFF

OFF

Event

 

 

SureCross MultiHop Data Radio

8

www.bannerengineering.com - tel: 763-544-3164

P/N 148947 Rev. C

Summary of Contents for SureCross DX80DR2M-H1

Page 1: ...y module IP67 NEMA 6 Inputs Four sinking discrete two 0 to 20 mA analog one thermistor one sinking counter Outputs Two NMOS discrete two switch power Serial interface RS 485 DX80DR9M H1E 10 to 30 V dc...

Page 2: ...op Master Radio Within a network of MultiHop data radios there is only one master radio The master radio controls the overall timing of the network and is always the parent device for other MultiHop r...

Page 3: ...duct Manual 151317 MultiHop Register Guide End User Edition 155289 Configure the DIP Switches Before making any changes to the DIP switch positions disconnect the power DIP switch changes will not be...

Page 4: ...ible to enable broadcast acknowledgement of the data packets to provide better throughput In transparent mode there is no access to the radio s I O Baud Rate and Parity The baud rate bits per second i...

Page 5: ...dc 10 to 30 V dc Tx RS 485 D1 B RS 485 D1 B V dc common GND dc common GND Rx RS 485 D0 A RS 485 D0 A B 3 6 to 5 5 V dc Wiring for DX80 E Radios Connecting dc power to the communication pins will cause...

Page 6: ...connection PWR Power 10 to 30 V dc power connection SPx Switch Power Provides variable power sources for external devices Discrete Input Wiring for PNP Sensors Discrete Input Wiring for NPN Sensors D...

Page 7: ...60 Modbus Register Maps Register 4xxxx Input Input Type Units I O Range Holding Register Representation Terminal Block Labels Min Value Max Value Min Dec Max Dec 1 1 Discrete IN 1 0 1 0 1 DI1 2 2 Dis...

Page 8: ...ut 2 output 1 etc Operation type specific parameters discrete counter analog 4 to 20 mA are grouped together based on the I O type number analog 1 analog 2 counter 1 etc Not all inputs or outputs may...

Page 9: ...Remove the four screws mounting the face plate to the housing and remove the face plate Do not remove the radio cover from the face plate 2 Remove the discharged battery and replace with a new battery...

Page 10: ...on covers Weight 0 26 kg 0 57 lbs M Hx and M HxC models Mounting 10 or M5 SS M5 hardware included M HxE models Mounting 1 4 inch or M7 SS M7 hardware included Max Tightening Torque 0 56 N m 5 lbf in I...

Page 11: ...BWA 9O2 C 900 MHz or BWA 2O2 C 2 4 GHz Antenna 2 dBd Omni Rubber Swivel RP SMA Male Not included with Internal antenna models Quick Start Guide 128185 for DX80 Gateways or 152653 for MultiHop models...

Page 12: ...ted Warranty Banner Engineering Corp warrants its products to be free from defects in material and workmanship for one year following the date of shipment Banner Engineering Corp will repair or replac...

Reviews: