Thermistor Inputs
Counter Inputs
AX2
GND
AX1
GND
Counter
Set the MultiHop Radio (Slave) ID
On a MultiHop radio, use the rotary dials to set the device’s MultiHop Radio ID.
Modbus Slave IDs 01 through 10 are reserved for slaves directly connected to the host (local
I/O). Polling messages addressed to these devices are not relayed over the wireless link. Use
Modbus Slave IDs 11 through 60 for MultiHop master, repeater, and slave radios. Up to 50
devices (local slaves and remote slaves) may be used in this system.
With the left dial acting as the left digit and the right dial acting as the right digit, the
MultiHop Radio ID can be set from 01 through 60.
Modbus Register Maps
Register
(4xxxx)
Input
#
Input Type
Units
I/O Range
Holding Register
Representation
Terminal
Block Labels
Min. Value Max.
Value
Min.
(Dec.)
Max.
(Dec.)
1
1
Discrete IN 1
-
0
1
0
1
DI1
2
2
Discrete IN 2
-
0
1
0
1
DI2
3
3
Discrete IN 3
-
0
1
0
1
DI3
4
4
Discrete IN 4
-
0
1
0
1
DI4
5
5
Analog IN 1
mA
0.0
20.0
0
65535
AI1
6
6
7
7
Analog IN 3
mA
0.0
20.0
0
65535
AI3
8
8
Thermistor
°F
-1638.3
+1638.4
-32768
32767
AX2
9
9
Counter IN 1
MSW 1
0
65535
0
65535
AX1
10
LSW 2
0
65535
0
65535
Register
(4xxxx)
Output
#
Output Type
Units
I/O Range
Holding Register
Representation
Terminal
Block Labels
Min. Value Max.
Value
Min.
(Dec.)
Max.
(Dec.)
501
1
Discrete OUT 1
-
0
1
0
1
DO1
502
2
Discrete OUT 2
-
0
1
0
1
DO2
503
3
504
4
1 Most Significant Word
2 Least Significant Word
SureCross MultiHop Data Radio
P/N 148947 Rev. C
www.bannerengineering.com - tel: 763-544-3164
7